<?xml version="1.0" encoding="UTF-8"?>
<!-- edited with XMLSpy v2014 (x64) (http://www.altova.com) by Robert Hitchcock (private) -->
<n1:AssetOMDocumentation xmlns:n1="http://data.ashrae.org/1801rp" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:schemaLocation="http://data.ashrae.org/1801rp file:///C:/Users/rjhit/Documents/ASHRAE/Asset%20Management/Project%20Docs/New%20docs/Schema/1801RPAssetOMDocumentation.xsd">
	<n1:EquipmentTypes>
		<n1:EquipmentType>
			<n1:uniqueID>d7a65520-ad87-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentTypeName>Boiler</n1:equipmentTypeName>
			<n1:equipmentOrSystemCategory>Boiler</n1:equipmentOrSystemCategory>
			<n1:manufacturer>Harsco</n1:manufacturer>
			<n1:manufacturerWebsite>www.harscopk.com</n1:manufacturerWebsite>
			<n1:vendorAgent>New England Air Systems</n1:vendorAgent>
			<n1:modelNumber>C-750</n1:modelNumber>
			<n1:warrantyGuarantorParts>Harsco</n1:warrantyGuarantorParts>
			<n1:warrantyDurationParts>12</n1:warrantyDurationParts>
			<n1:warrantyGuarantorLabor>Harsco</n1:warrantyGuarantorLabor>
			<n1:warrantyDurationLabor>12</n1:warrantyDurationLabor>
			<n1:warrantyDescription>Parts and Labor on Equipment</n1:warrantyDescription>
			<n1:listiomInstructionsUniqueID>25 52 16</n1:listiomInstructionsUniqueID>
			<n1:specificationSystem>CSI</n1:specificationSystem>
			<n1:specificationSection>25 52 16</n1:specificationSection>
			<n1:ULApproval>true</n1:ULApproval>
			<n1:additionalTechnicalDetails>none</n1:additionalTechnicalDetails>
			<n1:features>none</n1:features>
			<n1:nominalLength>41.00</n1:nominalLength>
			<n1:nominalWidth>28.00</n1:nominalWidth>
			<n1:nominalHeight>54.00</n1:nominalHeight>
			<n1:grossWeight>895.00</n1:grossWeight>
			<n1:shippingWeight>800.00</n1:shippingWeight>
			<n1:accessClearanceTop>24.00</n1:accessClearanceTop>
			<n1:accessClearanceBottom>0.00</n1:accessClearanceBottom>
			<n1:accessClearanceLeft>24.00</n1:accessClearanceLeft>
			<n1:accessClearanceRight>24.00</n1:accessClearanceRight>
			<n1:accessClearanceFront>36.00</n1:accessClearanceFront>
			<n1:accessClearanceRear>12.00</n1:accessClearanceRear>
			<n1:startingCurrent>10.00</n1:startingCurrent>
			<n1:fullLoadCurrent>6.00</n1:fullLoadCurrent>
			<n1:voltage>120.00</n1:voltage>
			<n1:frequency>60.00</n1:frequency>
			<n1:numberOfPhases>single phase</n1:numberOfPhases>
			<n1:maximumPowerConsumption>720.0</n1:maximumPowerConsumption>
			<n1:minimumPowerConsumption>300.0</n1:minimumPowerConsumption>
			<n1:expectedLife>15</n1:expectedLife>
			<n1:expectedLifeUnit>years</n1:expectedLifeUnit>
		</n1:EquipmentType>
		<n1:EquipmentType>
			<n1:uniqueID>d7a65764-ad87-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentTypeName>ControlSystem</n1:equipmentTypeName>
			<n1:equipmentOrSystemCategory>Control System</n1:equipmentOrSystemCategory>
			<n1:manufacturer>Siemens</n1:manufacturer>
			<n1:manufacturerWebsite>www.siemens.com</n1:manufacturerWebsite>
			<n1:vendorAgent>Siemens</n1:vendorAgent>
			<n1:modelNumber>Contract Number 440P231283</n1:modelNumber>
			<n1:warrantyGuarantorParts>Siemens</n1:warrantyGuarantorParts>
			<n1:warrantyDurationParts>12</n1:warrantyDurationParts>
			<n1:warrantyGuarantorLabor>Siemens</n1:warrantyGuarantorLabor>
			<n1:warrantyDurationLabor>12</n1:warrantyDurationLabor>
			<n1:warrantyDescription>System Hardware and Software</n1:warrantyDescription>
			<n1:listiomInstructionsUniqueID>25 50 00</n1:listiomInstructionsUniqueID>
			<n1:specificationSystem>CSI</n1:specificationSystem>
			<n1:specificationSection>25 50 00</n1:specificationSection>
			<n1:ULApproval>true</n1:ULApproval>
			<n1:additionalTechnicalDetails>none</n1:additionalTechnicalDetails>
			<n1:features>none</n1:features>
			<n1:nominalLength>36.00</n1:nominalLength>
			<n1:nominalWidth>18.00</n1:nominalWidth>
			<n1:nominalHeight>48.00</n1:nominalHeight>
			<n1:grossWeight>300.00</n1:grossWeight>
			<n1:shippingWeight>300.00</n1:shippingWeight>
			<n1:accessClearanceTop>36.00</n1:accessClearanceTop>
			<n1:accessClearanceBottom>48.00</n1:accessClearanceBottom>
			<n1:accessClearanceLeft>36.00</n1:accessClearanceLeft>
			<n1:accessClearanceRight>36.00</n1:accessClearanceRight>
			<n1:accessClearanceFront>36.00</n1:accessClearanceFront>
			<n1:accessClearanceRear>0.00</n1:accessClearanceRear>
			<n1:startingCurrent>20.00</n1:startingCurrent>
			<n1:fullLoadCurrent>20.00</n1:fullLoadCurrent>
			<n1:voltage>120.00</n1:voltage>
			<n1:frequency>60.00</n1:frequency>
			<n1:numberOfPhases>single phase</n1:numberOfPhases>
			<n1:maximumPowerConsumption>200.0</n1:maximumPowerConsumption>
			<n1:minimumPowerConsumption>200.0</n1:minimumPowerConsumption>
			<n1:expectedLife>15</n1:expectedLife>
			<n1:expectedLifeUnit>years</n1:expectedLifeUnit>
		</n1:EquipmentType>
		<n1:EquipmentType>
			<n1:uniqueID>d7a65ad4-ad87-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentTypeName>EnergyRecoveryUnit</n1:equipmentTypeName>
			<n1:equipmentOrSystemCategory>Economizer-Air side</n1:equipmentOrSystemCategory>
			<n1:manufacturer>MAFNA Air Technologies</n1:manufacturer>
			<n1:manufacturerWebsite>www.mafna.com</n1:manufacturerWebsite>
			<n1:vendorAgent>Mafna Technologies</n1:vendorAgent>
			<n1:modelNumber>Series 9000</n1:modelNumber>
			<n1:warrantyGuarantorParts>MAFNA Air Technologies</n1:warrantyGuarantorParts>
			<n1:warrantyDurationParts>12</n1:warrantyDurationParts>
			<n1:warrantyGuarantorLabor>MAFNA Air Technologies</n1:warrantyGuarantorLabor>
			<n1:warrantyDurationLabor>12</n1:warrantyDurationLabor>
			<n1:warrantyDescription>Parts and Labor on Equipment</n1:warrantyDescription>
			<n1:listiomInstructionsUniqueID>23 72 13</n1:listiomInstructionsUniqueID>
			<n1:specificationSystem>CSI</n1:specificationSystem>
			<n1:specificationSection>23 72 13</n1:specificationSection>
			<n1:ULApproval>true</n1:ULApproval>
			<n1:additionalTechnicalDetails>none</n1:additionalTechnicalDetails>
			<n1:features>none</n1:features>
			<n1:nominalLength>324.00</n1:nominalLength>
			<n1:nominalWidth>72.00</n1:nominalWidth>
			<n1:nominalHeight>96.00</n1:nominalHeight>
			<n1:grossWeight>2555.00</n1:grossWeight>
			<n1:shippingWeight>2800.00</n1:shippingWeight>
			<n1:accessClearanceTop>36.00</n1:accessClearanceTop>
			<n1:accessClearanceBottom>0.00</n1:accessClearanceBottom>
			<n1:accessClearanceLeft>48.00</n1:accessClearanceLeft>
			<n1:accessClearanceRight>48.00</n1:accessClearanceRight>
			<n1:accessClearanceFront>48.00</n1:accessClearanceFront>
			<n1:accessClearanceRear>48.00</n1:accessClearanceRear>
			<n1:startingCurrent>30.00</n1:startingCurrent>
			<n1:fullLoadCurrent>23.50</n1:fullLoadCurrent>
			<n1:voltage>460.00</n1:voltage>
			<n1:frequency>60.00</n1:frequency>
			<n1:numberOfPhases>three phase</n1:numberOfPhases>
			<n1:maximumPowerConsumption>20000.0</n1:maximumPowerConsumption>
			<n1:minimumPowerConsumption>19000.0</n1:minimumPowerConsumption>
			<n1:expectedLife>20</n1:expectedLife>
			<n1:expectedLifeUnit>years</n1:expectedLifeUnit>
		</n1:EquipmentType>
		<n1:EquipmentType>
			<n1:uniqueID>d7a65c28-ad87-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentTypeName>PackagedUnit</n1:equipmentTypeName>
			<n1:equipmentOrSystemCategory>Rooftop Unit</n1:equipmentOrSystemCategory>
			<n1:manufacturer>Trane</n1:manufacturer>
			<n1:manufacturerWebsite>www.trane.com</n1:manufacturerWebsite>
			<n1:vendorAgent>Alliance Mechanical</n1:vendorAgent>
			<n1:modelNumber>YHD150G4RVA-K60000000000b00000000000000</n1:modelNumber>
			<n1:warrantyGuarantorParts>Trane</n1:warrantyGuarantorParts>
			<n1:warrantyDurationParts>12</n1:warrantyDurationParts>
			<n1:warrantyGuarantorLabor>Trane</n1:warrantyGuarantorLabor>
			<n1:warrantyDurationLabor>12</n1:warrantyDurationLabor>
			<n1:warrantyDescription>Parts and Labor on Equipment</n1:warrantyDescription>
			<n1:listiomInstructionsUniqueID>23 74 33</n1:listiomInstructionsUniqueID>
			<n1:specificationSystem>CSI</n1:specificationSystem>
			<n1:specificationSection>23 74 33</n1:specificationSection>
			<n1:ULApproval>true</n1:ULApproval>
			<n1:additionalTechnicalDetails>none</n1:additionalTechnicalDetails>
			<n1:features>none</n1:features>
			<n1:nominalLength>122.00</n1:nominalLength>
			<n1:nominalWidth>85.00</n1:nominalWidth>
			<n1:nominalHeight>56.00</n1:nominalHeight>
			<n1:grossWeight>2351.00</n1:grossWeight>
			<n1:shippingWeight>2402.00</n1:shippingWeight>
			<n1:accessClearanceTop>48.00</n1:accessClearanceTop>
			<n1:accessClearanceBottom>0.00</n1:accessClearanceBottom>
			<n1:accessClearanceLeft>48.00</n1:accessClearanceLeft>
			<n1:accessClearanceRight>48.00</n1:accessClearanceRight>
			<n1:accessClearanceFront>48.00</n1:accessClearanceFront>
			<n1:accessClearanceRear>48.00</n1:accessClearanceRear>
			<n1:startingCurrent>40.00</n1:startingCurrent>
			<n1:fullLoadCurrent>30.00</n1:fullLoadCurrent>
			<n1:voltage>460.00</n1:voltage>
			<n1:frequency>60.00</n1:frequency>
			<n1:numberOfPhases>three phase</n1:numberOfPhases>
			<n1:maximumPowerConsumption>25000.0</n1:maximumPowerConsumption>
			<n1:minimumPowerConsumption>23000.0</n1:minimumPowerConsumption>
			<n1:expectedLife>20</n1:expectedLife>
			<n1:expectedLifeUnit>years</n1:expectedLifeUnit>
		</n1:EquipmentType>
		<n1:EquipmentType>
			<n1:uniqueID>d7a65d5e-ad87-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentTypeName>Pump</n1:equipmentTypeName>
			<n1:equipmentOrSystemCategory>Pump</n1:equipmentOrSystemCategory>
			<n1:manufacturer>Taco</n1:manufacturer>
			<n1:manufacturerWebsite>www.taco.com</n1:manufacturerWebsite>
			<n1:vendorAgent>Postler and Jaeckle</n1:vendorAgent>
			<n1:modelNumber>F12009C</n1:modelNumber>
			<n1:warrantyGuarantorParts>Taco</n1:warrantyGuarantorParts>
			<n1:warrantyDurationParts>12</n1:warrantyDurationParts>
			<n1:warrantyGuarantorLabor>Taco</n1:warrantyGuarantorLabor>
			<n1:warrantyDurationLabor>12</n1:warrantyDurationLabor>
			<n1:warrantyDescription>Parts and Labor on Equipment</n1:warrantyDescription>
			<n1:listiomInstructionsUniqueID>23 21 23.16</n1:listiomInstructionsUniqueID>
			<n1:specificationSystem>CSI</n1:specificationSystem>
			<n1:specificationSection>23 21 23.16</n1:specificationSection>
			<n1:ULApproval>true</n1:ULApproval>
			<n1:additionalTechnicalDetails>none</n1:additionalTechnicalDetails>
			<n1:features>none</n1:features>
			<n1:nominalLength>40.00</n1:nominalLength>
			<n1:nominalWidth>17.00</n1:nominalWidth>
			<n1:nominalHeight>21.00</n1:nominalHeight>
			<n1:grossWeight>350.00</n1:grossWeight>
			<n1:shippingWeight>350.00</n1:shippingWeight>
			<n1:accessClearanceTop>24.00</n1:accessClearanceTop>
			<n1:accessClearanceBottom>0.00</n1:accessClearanceBottom>
			<n1:accessClearanceLeft>24.00</n1:accessClearanceLeft>
			<n1:accessClearanceRight>24.00</n1:accessClearanceRight>
			<n1:accessClearanceFront>24.00</n1:accessClearanceFront>
			<n1:accessClearanceRear>24.00</n1:accessClearanceRear>
			<n1:startingCurrent>25.00</n1:startingCurrent>
			<n1:fullLoadCurrent>7.60</n1:fullLoadCurrent>
			<n1:voltage>460.00</n1:voltage>
			<n1:frequency>60.00</n1:frequency>
			<n1:numberOfPhases>three phase</n1:numberOfPhases>
			<n1:maximumPowerConsumption>6000.0</n1:maximumPowerConsumption>
			<n1:minimumPowerConsumption>3000.0</n1:minimumPowerConsumption>
			<n1:expectedLife>15</n1:expectedLife>
			<n1:expectedLifeUnit>years</n1:expectedLifeUnit>
		</n1:EquipmentType>
		<n1:EquipmentType>
			<n1:uniqueID>c3e652c2-b310-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentTypeName>AirHandler</n1:equipmentTypeName>
			<n1:equipmentOrSystemCategory>Air Handler</n1:equipmentOrSystemCategory>
			<n1:manufacturer>MAFNA Air Technologies</n1:manufacturer>
			<n1:manufacturerWebsite>www.mafnair.com</n1:manufacturerWebsite>
			<n1:vendorAgent>MAFNA Air Technologies</n1:vendorAgent>
			<n1:modelNumber>15.2202-CGH-AHU-1</n1:modelNumber>
			<n1:warrantyGuarantorParts>MAFNA Air Technologies</n1:warrantyGuarantorParts>
			<n1:warrantyDurationParts>12</n1:warrantyDurationParts>
			<n1:warrantyGuarantorLabor>MAFNA Air Technologies</n1:warrantyGuarantorLabor>
			<n1:warrantyDurationLabor>12</n1:warrantyDurationLabor>
			<n1:warrantyDescription>Parts and Labor on Equipment</n1:warrantyDescription>
			<n1:listiomInstructionsUniqueID>23 01 30</n1:listiomInstructionsUniqueID>
			<n1:specificationSystem>CSI</n1:specificationSystem>
			<n1:specificationSection>23 73 13</n1:specificationSection>
			<n1:ULApproval>true</n1:ULApproval>
			<n1:additionalTechnicalDetails>none</n1:additionalTechnicalDetails>
			<n1:features>none</n1:features>
			<n1:nominalLength>324.00</n1:nominalLength>
			<n1:nominalWidth>72.00</n1:nominalWidth>
			<n1:nominalHeight>96.00</n1:nominalHeight>
			<n1:grossWeight>11000.00</n1:grossWeight>
			<n1:shippingWeight>11340.00</n1:shippingWeight>
			<n1:accessClearanceTop>48.00</n1:accessClearanceTop>
			<n1:accessClearanceBottom>0.00</n1:accessClearanceBottom>
			<n1:accessClearanceLeft>48.00</n1:accessClearanceLeft>
			<n1:accessClearanceRight>48.00</n1:accessClearanceRight>
			<n1:accessClearanceFront>48.00</n1:accessClearanceFront>
			<n1:accessClearanceRear>0.00</n1:accessClearanceRear>
			<n1:startingCurrent>90.00</n1:startingCurrent>
			<n1:fullLoadCurrent>23.50</n1:fullLoadCurrent>
			<n1:voltage>460.00</n1:voltage>
			<n1:frequency>60.00</n1:frequency>
			<n1:numberOfPhases>three phase</n1:numberOfPhases>
			<n1:maximumPowerConsumption>19000.0</n1:maximumPowerConsumption>
			<n1:minimumPowerConsumption>10000.0</n1:minimumPowerConsumption>
			<n1:expectedLife>20</n1:expectedLife>
			<n1:expectedLifeUnit>years</n1:expectedLifeUnit>
		</n1:EquipmentType>
		<n1:EquipmentType>
			<n1:uniqueID>c3e6575e-b310-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentTypeName>CoolingCoil</n1:equipmentTypeName>
			<n1:equipmentOrSystemCategory>Coil</n1:equipmentOrSystemCategory>
			<n1:manufacturer>Aerofin</n1:manufacturer>
			<n1:manufacturerWebsite>www.aerofin.com</n1:manufacturerWebsite>
			<n1:vendorAgent>MAFNA Air Technologies</n1:vendorAgent>
			<n1:modelNumber>W-10.0AW-30.0x56.0-8-0.666</n1:modelNumber>
			<n1:warrantyGuarantorParts>MAFNA Air Technologies</n1:warrantyGuarantorParts>
			<n1:warrantyDurationParts>12</n1:warrantyDurationParts>
			<n1:warrantyGuarantorLabor>MAFNA Air Technologies</n1:warrantyGuarantorLabor>
			<n1:warrantyDurationLabor>12</n1:warrantyDurationLabor>
			<n1:warrantyDescription>Parts and Labor on Equipment</n1:warrantyDescription>
			<n1:listiomInstructionsUniqueID>23 01 30</n1:listiomInstructionsUniqueID>
			<n1:specificationSystem>CSI</n1:specificationSystem>
			<n1:specificationSection>23 82 16</n1:specificationSection>
			<n1:ULApproval>true</n1:ULApproval>
			<n1:additionalTechnicalDetails>none</n1:additionalTechnicalDetails>
			<n1:features>none</n1:features>
			<n1:nominalLength> 12.50 </n1:nominalLength>
			<n1:nominalWidth> 59.00 </n1:nominalWidth>
			<n1:nominalHeight> 33.00 </n1:nominalHeight>
			<n1:grossWeight> 447.00 </n1:grossWeight>
			<n1:shippingWeight> 447.00 </n1:shippingWeight>
			<n1:accessClearanceTop>0.00</n1:accessClearanceTop>
			<n1:accessClearanceBottom>0.00</n1:accessClearanceBottom>
			<n1:accessClearanceLeft> 36.00 </n1:accessClearanceLeft>
			<n1:accessClearanceRight> 36.00 </n1:accessClearanceRight>
			<n1:accessClearanceFront> 36.00 </n1:accessClearanceFront>
			<n1:accessClearanceRear> 36.00 </n1:accessClearanceRear>
			<n1:expectedLife>20</n1:expectedLife>
			<n1:expectedLifeUnit>years</n1:expectedLifeUnit>
		</n1:EquipmentType>
		<n1:EquipmentType>
			<n1:uniqueID>c3e6598e-b310-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentTypeName>HeatingCoil</n1:equipmentTypeName>
			<n1:equipmentOrSystemCategory>Coil</n1:equipmentOrSystemCategory>
			<n1:manufacturer>Aerofin</n1:manufacturer>
			<n1:manufacturerWebsite>www.aerofin.com</n1:manufacturerWebsite>
			<n1:vendorAgent>MAFNA Air Technologies</n1:vendorAgent>
			<n1:modelNumber>HW-5.0AS-24x56.0-1-0.25</n1:modelNumber>
			<n1:warrantyGuarantorParts>MAFNA Air Technologies</n1:warrantyGuarantorParts>
			<n1:warrantyDurationParts>12</n1:warrantyDurationParts>
			<n1:warrantyGuarantorLabor>MAFNA Air Technologies</n1:warrantyGuarantorLabor>
			<n1:warrantyDurationLabor>12</n1:warrantyDurationLabor>
			<n1:warrantyDescription>Parts and Labor on Equipment</n1:warrantyDescription>
			<n1:listiomInstructionsUniqueID>23 01 30</n1:listiomInstructionsUniqueID>
			<n1:specificationSystem>CSI</n1:specificationSystem>
			<n1:specificationSection>23 82 16</n1:specificationSection>
			<n1:ULApproval>true</n1:ULApproval>
			<n1:additionalTechnicalDetails>none</n1:additionalTechnicalDetails>
			<n1:features>none</n1:features>
			<n1:nominalLength> 6.00 </n1:nominalLength>
			<n1:nominalWidth> 59.00 </n1:nominalWidth>
			<n1:nominalHeight> 30.00 </n1:nominalHeight>
			<n1:grossWeight> 109.00 </n1:grossWeight>
			<n1:shippingWeight> 109.00 </n1:shippingWeight>
			<n1:accessClearanceTop>0.00</n1:accessClearanceTop>
			<n1:accessClearanceBottom>0.00</n1:accessClearanceBottom>
			<n1:accessClearanceLeft> 36.00 </n1:accessClearanceLeft>
			<n1:accessClearanceRight> 36.00 </n1:accessClearanceRight>
			<n1:accessClearanceFront> 36.00 </n1:accessClearanceFront>
			<n1:accessClearanceRear> 36.00 </n1:accessClearanceRear>
			<n1:expectedLife>20</n1:expectedLife>
			<n1:expectedLifeUnit>years</n1:expectedLifeUnit>
		</n1:EquipmentType>
		<n1:EquipmentType>
			<n1:uniqueID>7bf3199e-cc1c-11e9-a32f-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentTypeName>HeatingCoil</n1:equipmentTypeName>
			<n1:equipmentOrSystemCategory>Coil</n1:equipmentOrSystemCategory>
			<n1:manufacturer>Aerofin</n1:manufacturer>
			<n1:manufacturerWebsite>www.aerofin.com</n1:manufacturerWebsite>
			<n1:vendorAgent>MAFNA Air Technologies</n1:vendorAgent>
			<n1:modelNumber>HW-7.0AW-27.0 X 56.0-2-0.333</n1:modelNumber>
			<n1:warrantyGuarantorParts>MAFNA Air Technologies</n1:warrantyGuarantorParts>
			<n1:warrantyDurationParts>12</n1:warrantyDurationParts>
			<n1:warrantyGuarantorLabor>MAFNA Air Technologies</n1:warrantyGuarantorLabor>
			<n1:warrantyDurationLabor>12</n1:warrantyDurationLabor>
			<n1:warrantyDescription>Parts and Labor on Equipment</n1:warrantyDescription>
			<n1:listiomInstructionsUniqueID>23 01 30</n1:listiomInstructionsUniqueID>
			<n1:specificationSystem>CSI</n1:specificationSystem>
			<n1:specificationSection>23 82 16</n1:specificationSection>
			<n1:ULApproval>true</n1:ULApproval>
			<n1:additionalTechnicalDetails>none</n1:additionalTechnicalDetails>
			<n1:features>none</n1:features>
			<n1:nominalLength> 6.00 </n1:nominalLength>
			<n1:nominalWidth> 59.00 </n1:nominalWidth>
			<n1:nominalHeight> 30.00 </n1:nominalHeight>
			<n1:grossWeight> 109.00 </n1:grossWeight>
			<n1:shippingWeight> 109.00 </n1:shippingWeight>
			<n1:accessClearanceTop>0.00</n1:accessClearanceTop>
			<n1:accessClearanceBottom>0.00</n1:accessClearanceBottom>
			<n1:accessClearanceLeft> 36.00 </n1:accessClearanceLeft>
			<n1:accessClearanceRight> 36.00 </n1:accessClearanceRight>
			<n1:accessClearanceFront> 36.00 </n1:accessClearanceFront>
			<n1:accessClearanceRear> 36.00 </n1:accessClearanceRear>
			<n1:expectedLife>20</n1:expectedLife>
			<n1:expectedLifeUnit>years</n1:expectedLifeUnit>
		</n1:EquipmentType>
		<n1:EquipmentType>
			<n1:uniqueID>c3e65be6-b310-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentTypeName>Fan</n1:equipmentTypeName>
			<n1:equipmentOrSystemCategory>Fan (e.g., Exhaust, Supply, Transfer Return)</n1:equipmentOrSystemCategory>
			<n1:manufacturer>Twin City</n1:manufacturer>
			<n1:manufacturerWebsite>www.tef.com</n1:manufacturerWebsite>
			<n1:vendorAgent>MAFNA Air Technologies</n1:vendorAgent>
			<n1:modelNumber>EQPN 182, Class III, Arrangement 4</n1:modelNumber>
			<n1:warrantyGuarantorParts>MAFNA Air Technologies</n1:warrantyGuarantorParts>
			<n1:warrantyDurationParts>12</n1:warrantyDurationParts>
			<n1:warrantyGuarantorLabor>MAFNA Air Technologies</n1:warrantyGuarantorLabor>
			<n1:warrantyDurationLabor>12</n1:warrantyDurationLabor>
			<n1:warrantyDescription>Parts and Labor on Equipment</n1:warrantyDescription>
			<n1:listiomInstructionsUniqueID>23 01 30</n1:listiomInstructionsUniqueID>
			<n1:specificationSystem>CSI</n1:specificationSystem>
			<n1:specificationSection>12 34 16</n1:specificationSection>
			<n1:ULApproval>true</n1:ULApproval>
			<n1:additionalTechnicalDetails>none</n1:additionalTechnicalDetails>
			<n1:features>none</n1:features>
			<n1:nominalLength> 24.00 </n1:nominalLength>
			<n1:nominalWidth> 24.00 </n1:nominalWidth>
			<n1:nominalHeight> 30.00 </n1:nominalHeight>
			<n1:grossWeight> 362.00 </n1:grossWeight>
			<n1:shippingWeight> 362.00 </n1:shippingWeight>
			<n1:accessClearanceTop>0.00</n1:accessClearanceTop>
			<n1:accessClearanceBottom>0.00</n1:accessClearanceBottom>
			<n1:accessClearanceLeft> 36.00 </n1:accessClearanceLeft>
			<n1:accessClearanceRight> 36.00 </n1:accessClearanceRight>
			<n1:accessClearanceFront> 36.00 </n1:accessClearanceFront>
			<n1:accessClearanceRear> 36.00 </n1:accessClearanceRear>
			<n1:expectedLife>20</n1:expectedLife>
			<n1:expectedLifeUnit>years</n1:expectedLifeUnit>
		</n1:EquipmentType>
		<n1:EquipmentType>
			<n1:uniqueID>7bf31ea8-cc1c-11e9-a32f-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentTypeName>Fan</n1:equipmentTypeName>
			<n1:equipmentOrSystemCategory>Fan (e.g., Exhaust, Supply, Transfer Return)</n1:equipmentOrSystemCategory>
			<n1:manufacturer>Twin City</n1:manufacturer>
			<n1:manufacturerWebsite>www.tcf.com</n1:manufacturerWebsite>
			<n1:vendorAgent>MAFNA Air Technologies</n1:vendorAgent>
			<n1:modelNumber>EPFN 182, Class II, Arrangement 4</n1:modelNumber>
			<n1:warrantyGuarantorParts>MAFNA Air Technologies</n1:warrantyGuarantorParts>
			<n1:warrantyDurationParts>12</n1:warrantyDurationParts>
			<n1:warrantyGuarantorLabor>MAFNA Air Technologies</n1:warrantyGuarantorLabor>
			<n1:warrantyDurationLabor>12</n1:warrantyDurationLabor>
			<n1:warrantyDescription>Parts and Labor on Equipment</n1:warrantyDescription>
			<n1:listiomInstructionsUniqueID>23 01 30</n1:listiomInstructionsUniqueID>
			<n1:specificationSystem>CSI</n1:specificationSystem>
			<n1:specificationSection>12 34 16</n1:specificationSection>
			<n1:ULApproval>true</n1:ULApproval>
			<n1:additionalTechnicalDetails>none</n1:additionalTechnicalDetails>
			<n1:features>none</n1:features>
			<n1:nominalLength> 20.00 </n1:nominalLength>
			<n1:nominalWidth> 20.00 </n1:nominalWidth>
			<n1:nominalHeight> 24.00 </n1:nominalHeight>
			<n1:grossWeight> 269.00 </n1:grossWeight>
			<n1:shippingWeight> 269.00 </n1:shippingWeight>
			<n1:accessClearanceTop>0.00</n1:accessClearanceTop>
			<n1:accessClearanceBottom>0.00</n1:accessClearanceBottom>
			<n1:accessClearanceLeft> 36.00 </n1:accessClearanceLeft>
			<n1:accessClearanceRight> 36.00 </n1:accessClearanceRight>
			<n1:accessClearanceFront> 36.00 </n1:accessClearanceFront>
			<n1:accessClearanceRear> 36.00 </n1:accessClearanceRear>
			<n1:expectedLife>20</n1:expectedLife>
			<n1:expectedLifeUnit>years</n1:expectedLifeUnit>
		</n1:EquipmentType>
		<n1:EquipmentType>
			<n1:uniqueID>c3e65d30-b310-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentTypeName>Motor</n1:equipmentTypeName>
			<n1:equipmentOrSystemCategory>Fan (e.g., Exhaust, Supply, Transfer Return)</n1:equipmentOrSystemCategory>
			<n1:manufacturer>Baldor</n1:manufacturer>
			<n1:manufacturerWebsite>www.baldor.com</n1:manufacturerWebsite>
			<n1:vendorAgent>MAFNA Air Technologies</n1:vendorAgent>
			<n1:modelNumber>10 HP, 3600 RPM, 460 Volt, 3-Phase, TEFC Enclosure, 215T Frame, VFD Rated</n1:modelNumber>
			<n1:warrantyGuarantorParts>MAFNA Air Technologies</n1:warrantyGuarantorParts>
			<n1:warrantyDurationParts>12</n1:warrantyDurationParts>
			<n1:warrantyGuarantorLabor>MAFNA Air Technologies</n1:warrantyGuarantorLabor>
			<n1:warrantyDurationLabor>12</n1:warrantyDurationLabor>
			<n1:warrantyDescription>Parts and Labor on Equipment</n1:warrantyDescription>
			<n1:listiomInstructionsUniqueID>23 01 30</n1:listiomInstructionsUniqueID>
			<n1:specificationSystem>CSI</n1:specificationSystem>
			<n1:specificationSection>23 05 13</n1:specificationSection>
			<n1:ULApproval>true</n1:ULApproval>
			<n1:additionalTechnicalDetails>none</n1:additionalTechnicalDetails>
			<n1:features>none</n1:features>
			<n1:nominalLength> 14.00 </n1:nominalLength>
			<n1:nominalWidth> 14.00 </n1:nominalWidth>
			<n1:nominalHeight> 12.00 </n1:nominalHeight>
			<n1:grossWeight> 80.00 </n1:grossWeight>
			<n1:shippingWeight> 80.00 </n1:shippingWeight>
			<n1:accessClearanceTop>0.00</n1:accessClearanceTop>
			<n1:accessClearanceBottom>0.00</n1:accessClearanceBottom>
			<n1:accessClearanceLeft> 24.00 </n1:accessClearanceLeft>
			<n1:accessClearanceRight> 24.00 </n1:accessClearanceRight>
			<n1:accessClearanceFront> 24.00 </n1:accessClearanceFront>
			<n1:accessClearanceRear> 18.00 </n1:accessClearanceRear>
			<n1:startingCurrent> 80.00 </n1:startingCurrent>
			<n1:fullLoadCurrent> 14.00 </n1:fullLoadCurrent>
			<n1:voltage> 460.00 </n1:voltage>
			<n1:frequency> 60.00 </n1:frequency>
			<n1:numberOfPhases>three phase</n1:numberOfPhases>
			<n1:maximumPowerConsumption>11200.0</n1:maximumPowerConsumption>
			<n1:minimumPowerConsumption>4.0</n1:minimumPowerConsumption>
			<n1:expectedLife>15</n1:expectedLife>
			<n1:expectedLifeUnit>years</n1:expectedLifeUnit>
		</n1:EquipmentType>
		<n1:EquipmentType>
			<n1:uniqueID>7bf32308-cc1c-11e9-a32f-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentTypeName>Motor</n1:equipmentTypeName>
			<n1:equipmentOrSystemCategory>Fan (e.g., Exhaust, Supply, Transfer Return)</n1:equipmentOrSystemCategory>
			<n1:manufacturer>Baldor</n1:manufacturer>
			<n1:manufacturerWebsite>www.baldor.com</n1:manufacturerWebsite>
			<n1:vendorAgent>MAFNA Air Technologies</n1:vendorAgent>
			<n1:modelNumber>5 HP, 1800 RPM, 460 Volt, 3-Phase, TEFC Enclosure, 184T Frame, VFD Rated</n1:modelNumber>
			<n1:warrantyGuarantorParts>MAFNA Air Technologies</n1:warrantyGuarantorParts>
			<n1:warrantyDurationParts>12</n1:warrantyDurationParts>
			<n1:warrantyGuarantorLabor>MAFNA Air Technologies</n1:warrantyGuarantorLabor>
			<n1:warrantyDurationLabor>12</n1:warrantyDurationLabor>
			<n1:warrantyDescription>Parts and Labor on Equipment</n1:warrantyDescription>
			<n1:listiomInstructionsUniqueID>23 01 30</n1:listiomInstructionsUniqueID>
			<n1:specificationSystem>CSI</n1:specificationSystem>
			<n1:specificationSection>23 05 13</n1:specificationSection>
			<n1:ULApproval>true</n1:ULApproval>
			<n1:additionalTechnicalDetails>none</n1:additionalTechnicalDetails>
			<n1:features>none</n1:features>
			<n1:nominalLength> 11.00 </n1:nominalLength>
			<n1:nominalWidth> 7.25 </n1:nominalWidth>
			<n1:nominalHeight> 9.00 </n1:nominalHeight>
			<n1:grossWeight> 45.00 </n1:grossWeight>
			<n1:shippingWeight> 45.00 </n1:shippingWeight>
			<n1:accessClearanceTop>0.00</n1:accessClearanceTop>
			<n1:accessClearanceBottom>0.00</n1:accessClearanceBottom>
			<n1:accessClearanceLeft> 24.00 </n1:accessClearanceLeft>
			<n1:accessClearanceRight> 24.00 </n1:accessClearanceRight>
			<n1:accessClearanceFront> 24.00 </n1:accessClearanceFront>
			<n1:accessClearanceRear> 18.00 </n1:accessClearanceRear>
			<n1:startingCurrent> 46.00 </n1:startingCurrent>
			<n1:fullLoadCurrent> 7.60 </n1:fullLoadCurrent>
			<n1:voltage> 460.00 </n1:voltage>
			<n1:frequency> 60.00 </n1:frequency>
			<n1:numberOfPhases>three phase</n1:numberOfPhases>
			<n1:maximumPowerConsumption>11200.0</n1:maximumPowerConsumption>
			<n1:minimumPowerConsumption>4.0</n1:minimumPowerConsumption>
			<n1:expectedLife>15</n1:expectedLife>
			<n1:expectedLifeUnit>years</n1:expectedLifeUnit>
		</n1:EquipmentType>
	</n1:EquipmentTypes>
	<n1:EquipmentComponents>
		<n1:EquipmentComponent>
			<n1:uniqueID>3465edb2-ae40-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentName>Boiler-1</n1:equipmentComponentName>
			<n1:equipmentTypeUniqueIDReference>d7a65520-ad87-11e9-a2a3-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:space>n/a</n1:space>
			<n1:location>Mechanical Room</n1:location>
			<n1:associatedSystemUniqueIDReference>n/a</n1:associatedSystemUniqueIDReference>
			<n1:listSubComponentUniqueID>n/a</n1:listSubComponentUniqueID>
			<n1:serialNumber>C-2322126</n1:serialNumber>
			<n1:purchaseOrderNumber>200683</n1:purchaseOrderNumber>
			<n1:purchaseOrderDate>2019-03-27</n1:purchaseOrderDate>
			<n1:newOrRebuit>New</n1:newOrRebuit>
			<n1:installationDate>2019-04-01</n1:installationDate>
			<n1:warrantyStartDate>2019-05-01</n1:warrantyStartDate>
			<n1:equipmentStatus>All Original</n1:equipmentStatus>
			<n1:seasonalOperation>false</n1:seasonalOperation>
			<n1:numberOfMonthsInOperation>12</n1:numberOfMonthsInOperation>
			<n1:annualRunhours>8760</n1:annualRunhours>
			<n1:removalDate>1800-01-01</n1:removalDate>
			<n1:removalReason>still in place</n1:removalReason>
			<n1:color>Standard</n1:color>
			<n1:finish>Standard</n1:finish>
			<n1:electricalPanelName>PP-1</n1:electricalPanelName>
			<n1:electricalPanelCircuit>2,4,6</n1:electricalPanelCircuit>
		</n1:EquipmentComponent>
		<n1:EquipmentComponent>
			<n1:uniqueID>3465f01e-ae40-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentName>ControlSystem-1</n1:equipmentComponentName>
			<n1:equipmentTypeUniqueIDReference>d7a65764-ad87-11e9-a2a3-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:location>Room 115A</n1:location>
			<n1:serialNumber>440P231283</n1:serialNumber>
			<n1:purchaseOrderNumber>440P231283</n1:purchaseOrderNumber>
			<n1:purchaseOrderDate>2018-08-13</n1:purchaseOrderDate>
			<n1:newOrRebuit>New</n1:newOrRebuit>
			<n1:installationDate>2018-11-12</n1:installationDate>
			<n1:warrantyStartDate>2018-12-15</n1:warrantyStartDate>
			<n1:equipmentStatus>All Original</n1:equipmentStatus>
			<n1:seasonalOperation>false</n1:seasonalOperation>
			<n1:numberOfMonthsInOperation>12</n1:numberOfMonthsInOperation>
			<n1:annualRunhours>8760</n1:annualRunhours>
			<n1:color>Standard</n1:color>
			<n1:finish>Standard</n1:finish>
			<n1:electricalPanelName>LEMP-CT7</n1:electricalPanelName>
			<n1:electricalPanelCircuit>1,3</n1:electricalPanelCircuit>
		</n1:EquipmentComponent>
		<n1:EquipmentComponent>
			<n1:uniqueID>3465f172-ae40-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentName>EnergyRecoveryUnit-1</n1:equipmentComponentName>
			<n1:equipmentTypeUniqueIDReference>d7a65ad4-ad87-11e9-a2a3-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:location>Mech. Penthouse</n1:location>
			<n1:serialNumber>15-2202-CGH-DOAS-1</n1:serialNumber>
			<n1:purchaseOrderNumber>029353-0368</n1:purchaseOrderNumber>
			<n1:purchaseOrderDate>2017-04-10</n1:purchaseOrderDate>
			<n1:newOrRebuit>New</n1:newOrRebuit>
			<n1:installationDate>2017-05-01</n1:installationDate>
			<n1:warrantyStartDate>2017-06-01</n1:warrantyStartDate>
			<n1:equipmentStatus>All Original</n1:equipmentStatus>
			<n1:seasonalOperation>false</n1:seasonalOperation>
			<n1:numberOfMonthsInOperation>12</n1:numberOfMonthsInOperation>
			<n1:annualRunhours>8760</n1:annualRunhours>
			<n1:color>Standard</n1:color>
			<n1:finish>Standard</n1:finish>
			<n1:electricalPanelName>HLRP-PH</n1:electricalPanelName>
			<n1:electricalPanelCircuit>2,4,6</n1:electricalPanelCircuit>
		</n1:EquipmentComponent>
		<n1:EquipmentComponent>
			<n1:uniqueID>3465f460-ae40-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentName>PackagedUnit-1</n1:equipmentComponentName>
			<n1:equipmentTypeUniqueIDReference>d7a65c28-ad87-11e9-a2a3-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:location>Roof</n1:location>
			<n1:serialNumber>f12E02758</n1:serialNumber>
			<n1:purchaseOrderNumber>16-6247.02</n1:purchaseOrderNumber>
			<n1:purchaseOrderDate>2017-05-04</n1:purchaseOrderDate>
			<n1:newOrRebuit>New</n1:newOrRebuit>
			<n1:installationDate>2017-07-01</n1:installationDate>
			<n1:warrantyStartDate>2017-09-01</n1:warrantyStartDate>
			<n1:equipmentStatus>All Original</n1:equipmentStatus>
			<n1:seasonalOperation>false</n1:seasonalOperation>
			<n1:numberOfMonthsInOperation>12</n1:numberOfMonthsInOperation>
			<n1:annualRunhours>8760</n1:annualRunhours>
			<n1:color>Standard</n1:color>
			<n1:finish>Standard</n1:finish>
			<n1:electricalPanelName>MDP-1</n1:electricalPanelName>
			<n1:electricalPanelCircuit>1,3,5</n1:electricalPanelCircuit>
		</n1:EquipmentComponent>
		<n1:EquipmentComponent>
			<n1:uniqueID>3465f5aa-ae40-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentName>Pump-1</n1:equipmentComponentName>
			<n1:equipmentTypeUniqueIDReference>d7a65d5e-ad87-11e9-a2a3-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:location>Mechanical Room</n1:location>
			<n1:serialNumber>45560216</n1:serialNumber>
			<n1:purchaseOrderNumber>13039</n1:purchaseOrderNumber>
			<n1:purchaseOrderDate>2015-06-17</n1:purchaseOrderDate>
			<n1:newOrRebuit>New</n1:newOrRebuit>
			<n1:installationDate>2015-11-15</n1:installationDate>
			<n1:warrantyStartDate>2016-02-01</n1:warrantyStartDate>
			<n1:equipmentStatus>All Original</n1:equipmentStatus>
			<n1:seasonalOperation>false</n1:seasonalOperation>
			<n1:numberOfMonthsInOperation>7</n1:numberOfMonthsInOperation>
			<n1:annualRunhours>4300</n1:annualRunhours>
			<n1:color>Standard</n1:color>
			<n1:finish>Standard</n1:finish>
			<n1:electricalPanelName>HDP-EM</n1:electricalPanelName>
			<n1:electricalPanelCircuit>1,3,5</n1:electricalPanelCircuit>
		</n1:EquipmentComponent>
		<n1:EquipmentComponent>
			<n1:uniqueID>9ba8eede-ae68-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentName>AirHandler-1</n1:equipmentComponentName>
			<n1:equipmentTypeUniqueIDReference>c3e652c2-b310-11e9-a2a3-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:location>Mechanical Room</n1:location>
			<n1:listSubComponentUniqueID>bd42aee0-b313-11e9-a2a3-2a2ae2dbcce4, bd42b1c4-b313-11e9-a2a3-2a2ae2dbcce4, bd42b638-b313-11e9-a2a3-2a2ae2dbcce4</n1:listSubComponentUniqueID>
			<n1:serialNumber>15.2202-CGH-AHU-1</n1:serialNumber>
			<n1:purchaseOrderNumber>16-6247.02</n1:purchaseOrderNumber>
			<n1:purchaseOrderDate>2017-05-04</n1:purchaseOrderDate>
			<n1:newOrRebuit>New</n1:newOrRebuit>
			<n1:installationDate>2017-07-01</n1:installationDate>
			<n1:warrantyStartDate>2017-09-01</n1:warrantyStartDate>
			<n1:equipmentStatus>All Original</n1:equipmentStatus>
			<n1:seasonalOperation>false</n1:seasonalOperation>
			<n1:numberOfMonthsInOperation>12</n1:numberOfMonthsInOperation>
			<n1:annualRunhours>8760</n1:annualRunhours>
			<n1:color>Standard</n1:color>
			<n1:finish>Standard</n1:finish>
			<n1:electricalPanelName>HDP-EM</n1:electricalPanelName>
			<n1:electricalPanelCircuit>2,4,6</n1:electricalPanelCircuit>
		</n1:EquipmentComponent>
		<n1:EquipmentComponent>
			<n1:uniqueID>bd42aee0-b313-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentName>CoolingCoil-1</n1:equipmentComponentName>
			<n1:equipmentTypeUniqueIDReference>c3e6575e-b310-11e9-a2a3-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:location>AirHandler-1</n1:location>
			<n1:associatedSystemUniqueIDReference>9ba8eede-ae68-11e9-a2a3-2a2ae2dbcce4</n1:associatedSystemUniqueIDReference>
			<n1:serialNumber>W-10.0AW-30.0x56.0-8-0.666</n1:serialNumber>
			<n1:purchaseOrderNumber>16-6247.02</n1:purchaseOrderNumber>
			<n1:purchaseOrderDate>2017-05-04</n1:purchaseOrderDate>
			<n1:newOrRebuit>New</n1:newOrRebuit>
			<n1:installationDate>2017-07-01</n1:installationDate>
			<n1:warrantyStartDate>2017-09-01</n1:warrantyStartDate>
			<n1:equipmentStatus>All Original</n1:equipmentStatus>
			<n1:seasonalOperation>false</n1:seasonalOperation>
			<n1:numberOfMonthsInOperation>12</n1:numberOfMonthsInOperation>
			<n1:annualRunhours>8760</n1:annualRunhours>
			<n1:color>Standard</n1:color>
			<n1:finish>Standard</n1:finish>
			<n1:electricalPanelName>n/a</n1:electricalPanelName>
			<n1:electricalPanelCircuit>n/a</n1:electricalPanelCircuit>
		</n1:EquipmentComponent>
		<n1:EquipmentComponent>
			<n1:uniqueID>bd42b1c4-b313-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentName>HeatingCoil-Preheat</n1:equipmentComponentName>
			<n1:equipmentTypeUniqueIDReference>c3e6598e-b310-11e9-a2a3-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:location>AirHandler-1</n1:location>
			<n1:associatedSystemUniqueIDReference>9ba8eede-ae68-11e9-a2a3-2a2ae2dbcce4</n1:associatedSystemUniqueIDReference>
			<n1:serialNumber>HW-5.0AS-24x56.0-1-0.25</n1:serialNumber>
			<n1:purchaseOrderNumber>16-6247.02</n1:purchaseOrderNumber>
			<n1:purchaseOrderDate>2017-05-04</n1:purchaseOrderDate>
			<n1:newOrRebuit>New</n1:newOrRebuit>
			<n1:installationDate>2017-07-01</n1:installationDate>
			<n1:warrantyStartDate>2017-09-01</n1:warrantyStartDate>
			<n1:equipmentStatus>All Original</n1:equipmentStatus>
			<n1:seasonalOperation>false</n1:seasonalOperation>
			<n1:numberOfMonthsInOperation>12</n1:numberOfMonthsInOperation>
			<n1:annualRunhours>8760</n1:annualRunhours>
			<n1:color>Standard</n1:color>
			<n1:finish>Standard</n1:finish>
			<n1:electricalPanelName>n/a</n1:electricalPanelName>
			<n1:electricalPanelCircuit>n/a</n1:electricalPanelCircuit>
		</n1:EquipmentComponent>
		<n1:EquipmentComponent>
			<n1:uniqueID>bd42b638-b313-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentName>Fan-Supply</n1:equipmentComponentName>
			<n1:equipmentTypeUniqueIDReference>c3e65be6-b310-11e9-a2a3-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:location>AirHandler-1</n1:location>
			<n1:associatedSystemUniqueIDReference>9ba8eede-ae68-11e9-a2a3-2a2ae2dbcce4</n1:associatedSystemUniqueIDReference>
			<n1:listSubComponentUniqueID>bd42b7aa-b313-11e9-a2a3-2a2ae2dbcce4</n1:listSubComponentUniqueID>
			<n1:serialNumber>EQPN 182, Class III, Arrangement 4</n1:serialNumber>
			<n1:purchaseOrderNumber>16-6247.02</n1:purchaseOrderNumber>
			<n1:purchaseOrderDate>2017-05-04</n1:purchaseOrderDate>
			<n1:newOrRebuit>New</n1:newOrRebuit>
			<n1:installationDate>2017-07-01</n1:installationDate>
			<n1:warrantyStartDate>2017-09-01</n1:warrantyStartDate>
			<n1:equipmentStatus>All Original</n1:equipmentStatus>
			<n1:seasonalOperation>false</n1:seasonalOperation>
			<n1:numberOfMonthsInOperation>12</n1:numberOfMonthsInOperation>
			<n1:annualRunhours>8760</n1:annualRunhours>
			<n1:color>Standard</n1:color>
			<n1:finish>Standard</n1:finish>
			<n1:electricalPanelName>n/a</n1:electricalPanelName>
			<n1:electricalPanelCircuit>n/a</n1:electricalPanelCircuit>
		</n1:EquipmentComponent>
		<n1:EquipmentComponent>
			<n1:uniqueID>bd42b7aa-b313-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentName>Motor-Fan-Supply</n1:equipmentComponentName>
			<n1:equipmentTypeUniqueIDReference>c3e65d30-b310-11e9-a2a3-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:location>Fan-Supply</n1:location>
			<n1:associatedSystemUniqueIDReference>bd42b638-b313-11e9-a2a3-2a2ae2dbcce4</n1:associatedSystemUniqueIDReference>
			<n1:serialNumber>10 HP, 3600 RPM, 460 Volt, 3-Phase, TEFC Enclosure, 215T Frame, VFD Rated</n1:serialNumber>
			<n1:purchaseOrderNumber>16-6247.02</n1:purchaseOrderNumber>
			<n1:purchaseOrderDate>2017-05-04</n1:purchaseOrderDate>
			<n1:newOrRebuit>New</n1:newOrRebuit>
			<n1:installationDate>2017-07-01</n1:installationDate>
			<n1:warrantyStartDate>2017-09-01</n1:warrantyStartDate>
			<n1:equipmentStatus>All Original</n1:equipmentStatus>
			<n1:seasonalOperation>false</n1:seasonalOperation>
			<n1:numberOfMonthsInOperation>12</n1:numberOfMonthsInOperation>
			<n1:annualRunhours>8760</n1:annualRunhours>
			<n1:color>Standard</n1:color>
			<n1:finish>Standard</n1:finish>
			<n1:electricalPanelName>HDP-EM</n1:electricalPanelName>
			<n1:electricalPanelCircuit>2,4,6</n1:electricalPanelCircuit>
		</n1:EquipmentComponent>
		<n1:EquipmentComponent>
			<n1:uniqueID>9705fda2-cc1f-11e9-a32f-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentName>HeatingCoil-Reheat</n1:equipmentComponentName>
			<n1:equipmentTypeUniqueIDReference>7bf3199e-cc1c-11e9-a32f-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:location>AirHandler-1</n1:location>
			<n1:associatedSystemUniqueIDReference>9ba8eede-ae68-11e9-a2a3-2a2ae2dbcce4</n1:associatedSystemUniqueIDReference>
			<n1:serialNumber>HW-7.0AW-27.0 X 56.0-2-0.333</n1:serialNumber>
			<n1:purchaseOrderNumber>16-6247.02</n1:purchaseOrderNumber>
			<n1:purchaseOrderDate>2017-05-04</n1:purchaseOrderDate>
			<n1:newOrRebuit>New</n1:newOrRebuit>
			<n1:installationDate>2017-07-01</n1:installationDate>
			<n1:warrantyStartDate>2017-09-01</n1:warrantyStartDate>
			<n1:equipmentStatus>All Original</n1:equipmentStatus>
			<n1:seasonalOperation>false</n1:seasonalOperation>
			<n1:numberOfMonthsInOperation>12</n1:numberOfMonthsInOperation>
			<n1:annualRunhours>8760</n1:annualRunhours>
			<n1:color>Standard</n1:color>
			<n1:finish>Standard</n1:finish>
			<n1:electricalPanelName>n/a</n1:electricalPanelName>
			<n1:electricalPanelCircuit>n/a</n1:electricalPanelCircuit>
		</n1:EquipmentComponent>
		<n1:EquipmentComponent>
			<n1:uniqueID>9705fffa-cc1f-11e9-a32f-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentName>Fan-Return</n1:equipmentComponentName>
			<n1:equipmentTypeUniqueIDReference>7bf31ea8-cc1c-11e9-a32f-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:space>n/a</n1:space>
			<n1:location>AirHandler-1</n1:location>
			<n1:associatedSystemUniqueIDReference>9ba8eede-ae68-11e9-a2a3-2a2ae2dbcce4</n1:associatedSystemUniqueIDReference>
			<n1:listSubComponentUniqueID>970601a8-cc1f-11e9-a32f-2a2ae2dbcce4</n1:listSubComponentUniqueID>
			<n1:serialNumber>EPFN 182, Class II, Arrangement 4</n1:serialNumber>
			<n1:purchaseOrderNumber>16-6247.02</n1:purchaseOrderNumber>
			<n1:purchaseOrderDate>2017-05-04</n1:purchaseOrderDate>
			<n1:newOrRebuit>New</n1:newOrRebuit>
			<n1:installationDate>2017-07-01</n1:installationDate>
			<n1:warrantyStartDate>2017-09-01</n1:warrantyStartDate>
			<n1:equipmentStatus>All Original</n1:equipmentStatus>
			<n1:seasonalOperation>false</n1:seasonalOperation>
			<n1:numberOfMonthsInOperation>12</n1:numberOfMonthsInOperation>
			<n1:annualRunhours>8760</n1:annualRunhours>
			<n1:color>Standard</n1:color>
			<n1:finish>Standard</n1:finish>
			<n1:electricalPanelName>n/a</n1:electricalPanelName>
			<n1:electricalPanelCircuit>n/a</n1:electricalPanelCircuit>
		</n1:EquipmentComponent>
		<n1:EquipmentComponent>
			<n1:uniqueID>970601a8-cc1f-11e9-a32f-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentName>Motor-Fan-Return</n1:equipmentComponentName>
			<n1:equipmentTypeUniqueIDReference>7bf32308-cc1c-11e9-a32f-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:location>Fan-Return</n1:location>
			<n1:associatedSystemUniqueIDReference>9705fffa-cc1f-11e9-a32f-2a2ae2dbcce4</n1:associatedSystemUniqueIDReference>
			<n1:serialNumber>5 HP, 1800 RPM, 460 Volt, 3-Phase, TEFC Enclosure, 184T Frame, VFD Rated</n1:serialNumber>
			<n1:purchaseOrderNumber>16-6247.02</n1:purchaseOrderNumber>
			<n1:purchaseOrderDate>2017-05-04</n1:purchaseOrderDate>
			<n1:newOrRebuit>New</n1:newOrRebuit>
			<n1:installationDate>2017-07-01</n1:installationDate>
			<n1:warrantyStartDate>2017-09-01</n1:warrantyStartDate>
			<n1:equipmentStatus>All Original</n1:equipmentStatus>
			<n1:seasonalOperation>false</n1:seasonalOperation>
			<n1:numberOfMonthsInOperation>12</n1:numberOfMonthsInOperation>
			<n1:annualRunhours>8760</n1:annualRunhours>
			<n1:color>Standard</n1:color>
			<n1:finish>Standard</n1:finish>
			<n1:electricalPanelName>HDP-EM</n1:electricalPanelName>
			<n1:electricalPanelCircuit>2,4,6</n1:electricalPanelCircuit>
		</n1:EquipmentComponent>
	</n1:EquipmentComponents>
	<n1:ExtendedPropertySets>
		<n1:AirHandlerPropertySet>
			<n1:uniqueID>68a89d04-ae68-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentUniqueIDReference>9ba8eede-ae68-11e9-a2a3-2a2ae2dbcce4</n1:equipmentComponentUniqueIDReference>
			<n1:options>Humidification, heat recovery wheel</n1:options>
			<n1:heatingMedium>steam</n1:heatingMedium>
			<n1:coolingMedium>chilled water</n1:coolingMedium>
			<n1:supplyAirFlowRate>40000</n1:supplyAirFlowRate>
			<n1:returnAirFlowRate>40000</n1:returnAirFlowRate>
			<n1:outdoorAirInletFlowRate>40000</n1:outdoorAirInletFlowRate>
			<n1:exhaustAirFlowRate>40000</n1:exhaustAirFlowRate>
			<n1:supplyStaticPressure>7</n1:supplyStaticPressure>
			<n1:totalHeatingCapacity>2608</n1:totalHeatingCapacity>
			<n1:totalCoolingCapacity>1526</n1:totalCoolingCapacity>
		</n1:AirHandlerPropertySet>
		<n1:BoilerPropertySet>
			<n1:uniqueID>ecf7f312-ae62-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentUniqueIDReference>3465edb2-ae40-11e9-a2a3-2a2ae2dbcce4</n1:equipmentComponentUniqueIDReference>
			<n1:boilerType>space heating</n1:boilerType>
			<n1:configuration>single</n1:configuration>
			<n1:shape>rectangular</n1:shape>
			<n1:mounting>floor standing</n1:mounting>
			<n1:burnerControlType>modulating</n1:burnerControlType>
			<n1:heaterOperation>condensing</n1:heaterOperation>
			<n1:heatExchangerMaterial>cast iron</n1:heatExchangerMaterial>
			<n1:fuelConnectionType>threaded</n1:fuelConnectionType>
			<n1:flowAndReturnConnectionType>flanged</n1:flowAndReturnConnectionType>
			<n1:drainConnectionType>threaded</n1:drainConnectionType>
			<n1:safetyValveConnectionType>threaded</n1:safetyValveConnectionType>
			<n1:condensateDrainType>gravity</n1:condensateDrainType>
			<n1:flueOrAirIntakeClassification>n/a</n1:flueOrAirIntakeClassification>
			<n1:fuelConnectionSize>1.00</n1:fuelConnectionSize>
			<n1:flowAndReturnConnectionSize>2.00</n1:flowAndReturnConnectionSize>
			<n1:drainConnectionSize>0.75</n1:drainConnectionSize>
			<n1:safetyValveConnectionSize>1.00</n1:safetyValveConnectionSize>
			<n1:condensateConnectionSize>0.75</n1:condensateConnectionSize>
			<n1:flueConnectionSize>6.00</n1:flueConnectionSize>
			<n1:airInletConnectionSize>6.00</n1:airInletConnectionSize>
			<n1:inputPower>750000</n1:inputPower>
			<n1:outputPower>704000</n1:outputPower>
			<n1:ventDiameter>6.00</n1:ventDiameter>
			<n1:passes>single pass</n1:passes>
			<n1:pressureDrop>2.00</n1:pressureDrop>
			<n1:fuelType>natural gas</n1:fuelType>
			<n1:heatingMedium>hot water</n1:heatingMedium>
			<n1:waterFlow>36.00</n1:waterFlow>
			<n1:enteringWaterTemperature>120.00</n1:enteringWaterTemperature>
			<n1:leavingWaterTempurature>194.00</n1:leavingWaterTempurature>
		</n1:BoilerPropertySet>
		<n1:ControlSystemPropertySet>
			<n1:uniqueID>1472f054-ae68-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentUniqueIDReference>3465f01e-ae40-11e9-a2a3-2a2ae2dbcce4</n1:equipmentComponentUniqueIDReference>
			<n1:controlSystemApplication>Energy Management System</n1:controlSystemApplication>
			<n1:controlSystemType>All Electric</n1:controlSystemType>
			<n1:controlSystemArchitecture>DDC</n1:controlSystemArchitecture>
			<n1:operatorInterface>PC Terminal</n1:operatorInterface>
			<n1:alarming>true</n1:alarming>
			<n1:trending>true</n1:trending>
			<n1:remoteAccess>true</n1:remoteAccess>
			<n1:controlSystemSoftware>Siemens</n1:controlSystemSoftware>
			<n1:instrumentationAndFieldDevices>Siemens</n1:instrumentationAndFieldDevices>
		</n1:ControlSystemPropertySet>
		<n1:CoolingCoilPropertySet>
			<n1:uniqueID>e32ff512-af09-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentUniqueIDReference>bd42aee0-b313-11e9-a2a3-2a2ae2dbcce4</n1:equipmentComponentUniqueIDReference>
			<n1:enteringAirTempuratureDB>78.50</n1:enteringAirTempuratureDB>
			<n1:enteringAirTempuratureWB>65.50</n1:enteringAirTempuratureWB>
			<n1:leavingAirTempuratureDB>53.00</n1:leavingAirTempuratureDB>
			<n1:leavingAirTempuratureWB>52.60</n1:leavingAirTempuratureWB>
			<n1:coolingMedium>chilled water</n1:coolingMedium>
			<n1:enteringCoolingMediumTempurature>45.00</n1:enteringCoolingMediumTempurature>
			<n1:leavingCoolingMediumTempurature>55.00</n1:leavingCoolingMediumTempurature>
			<n1:coolingMediumFlowRate>296.19</n1:coolingMediumFlowRate>
			<n1:coilAirPressureDrop>0.04</n1:coilAirPressureDrop>
			<n1:coilCoolingMediumPressureDrop>8.69</n1:coilCoolingMediumPressureDrop>
			<n1:airVelocity>419.30</n1:airVelocity>
			<n1:coolingCapacity>1503.60</n1:coolingCapacity>
		</n1:CoolingCoilPropertySet>
		<n1:EnergyRecoveryUnitPropertySet>
			<n1:uniqueID>babd64fe-af02-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentUniqueIDReference>3465f172-ae40-11e9-a2a3-2a2ae2dbcce4</n1:equipmentComponentUniqueIDReference>
			<n1:options>n/a</n1:options>
			<n1:eruType>enthalpy wheel</n1:eruType>
			<n1:enteringAirTempuratureDB>90</n1:enteringAirTempuratureDB>
			<n1:enteringAirTempuratureWB>73</n1:enteringAirTempuratureWB>
			<n1:leavingAirTempuratureDB>78</n1:leavingAirTempuratureDB>
			<n1:leavingAirTempuratureWB>67</n1:leavingAirTempuratureWB>
			<n1:enteringCoolingMediumTempurature>76</n1:enteringCoolingMediumTempurature>
			<n1:leavingCoolingMediumTempurature>87.3</n1:leavingCoolingMediumTempurature>
			<n1:eruAirPressureDrop>0.7</n1:eruAirPressureDrop>
			<n1:airFlowRate>4200</n1:airFlowRate>
			<n1:faceVelocity>579</n1:faceVelocity>
			<n1:eruCapacity>0.094</n1:eruCapacity>
		</n1:EnergyRecoveryUnitPropertySet>
		<n1:FanPropertySet>
			<n1:uniqueID>9c1c7022-af0b-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentUniqueIDReference>bd42b638-b313-11e9-a2a3-2a2ae2dbcce4</n1:equipmentComponentUniqueIDReference>
			<n1:driveType>direct</n1:driveType>
			<n1:flowMaximum>10000.00</n1:flowMaximum>
			<n1:flowNominal>10000.00</n1:flowNominal>
			<n1:staticPressure>7.83</n1:staticPressure>
			<n1:soundLevel>95.00</n1:soundLevel>
		</n1:FanPropertySet>
		<n1:FanPropertySet>
			<n1:uniqueID>9c1c7482-af0b-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentUniqueIDReference>9705fffa-cc1f-11e9-a32f-2a2ae2dbcce4</n1:equipmentComponentUniqueIDReference>
			<n1:driveType>direct</n1:driveType>
			<n1:flowMaximum>14082.00</n1:flowMaximum>
			<n1:flowNominal>14082.00</n1:flowNominal>
			<n1:staticPressure>4.94</n1:staticPressure>
			<n1:soundLevel>94.00</n1:soundLevel>
		</n1:FanPropertySet>
		<n1:HeatingCoilPropertySet>
			<n1:uniqueID>3531674c-af0a-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentUniqueIDReference>bd42b1c4-b313-11e9-a2a3-2a2ae2dbcce4</n1:equipmentComponentUniqueIDReference>
			<n1:enteringAirTempuratureDB>-5.00</n1:enteringAirTempuratureDB>
			<n1:enteringAirTempuratureWB>0.00</n1:enteringAirTempuratureWB>
			<n1:leavingAirTempuratureDB>70.00</n1:leavingAirTempuratureDB>
			<n1:leavingAirTempuratureWB>62.00</n1:leavingAirTempuratureWB>
			<n1:heatingMedium>steam</n1:heatingMedium>
			<n1:enteringHeatingMediumTempurature>212.00</n1:enteringHeatingMediumTempurature>
			<n1:leavingHeatingMediumTempurature>180.00</n1:leavingHeatingMediumTempurature>
			<n1:heatingMediumFlowRate>3271.00</n1:heatingMediumFlowRate>
			<n1:heatingMediumFlowRateUnits>lbs/hour</n1:heatingMediumFlowRateUnits>
			<n1:coilAirPressureDrop>0.28</n1:coilAirPressureDrop>
			<n1:coilHeatingMediumPressureDrop>10.00</n1:coilHeatingMediumPressureDrop>
			<n1:airVelocity>885.20</n1:airVelocity>
			<n1:heatingCapacity>3123.60</n1:heatingCapacity>
		</n1:HeatingCoilPropertySet>
		<n1:HeatingCoilPropertySet>
			<n1:uniqueID>3e6032a8-af0a-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentUniqueIDReference>9705fda2-cc1f-11e9-a32f-2a2ae2dbcce4</n1:equipmentComponentUniqueIDReference>
			<n1:enteringAirTempuratureDB>58.00</n1:enteringAirTempuratureDB>
			<n1:enteringAirTempuratureWB>53.00</n1:enteringAirTempuratureWB>
			<n1:leavingAirTempuratureDB>70.00</n1:leavingAirTempuratureDB>
			<n1:leavingAirTempuratureWB>62.00</n1:leavingAirTempuratureWB>
			<n1:heatingMedium>steam</n1:heatingMedium>
			<n1:enteringHeatingMediumTempurature>212.00</n1:enteringHeatingMediumTempurature>
			<n1:leavingHeatingMediumTempurature>180.00</n1:leavingHeatingMediumTempurature>
			<n1:heatingMediumFlowRate>2603.60</n1:heatingMediumFlowRate>
			<n1:heatingMediumFlowRateUnits>lbs/hour</n1:heatingMediumFlowRateUnits>
			<n1:coilAirPressureDrop>0.28</n1:coilAirPressureDrop>
			<n1:coilHeatingMediumPressureDrop>10.00</n1:coilHeatingMediumPressureDrop>
			<n1:airVelocity>885.20</n1:airVelocity>
			<n1:heatingCapacity>2486.00</n1:heatingCapacity>
		</n1:HeatingCoilPropertySet>
		<n1:MotorPropertySet>
			<n1:uniqueID>c7c883e2-af05-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentUniqueIDReference>bd42b7aa-b313-11e9-a2a3-2a2ae2dbcce4</n1:equipmentComponentUniqueIDReference>
			<n1:application>AHU</n1:application>
			<n1:motorType>Induction</n1:motorType>
			<n1:outputPower>20.00</n1:outputPower>
			<n1:speedControl>variable speed</n1:speedControl>
			<n1:speed>1765.00</n1:speed>
			<n1:frameSize>256T</n1:frameSize>
			<n1:enclosureType>TEFC</n1:enclosureType>
			<n1:serviceFactor>1.15</n1:serviceFactor>
			<n1:lockedRotorKVACode>H</n1:lockedRotorKVACode>
			<n1:NEMANominalEfficiency>93.0</n1:NEMANominalEfficiency>
			<n1:torqueCurrentCharacteristics>A</n1:torqueCurrentCharacteristics>
			<n1:duty>continuous</n1:duty>
			<n1:insulationClass>F</n1:insulationClass>
			<n1:maximumAmbientTemperature>104.00</n1:maximumAmbientTemperature>
		</n1:MotorPropertySet>
		<n1:MotorPropertySet>
			<n1:uniqueID>c7c88734-af05-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentUniqueIDReference>970601a8-cc1f-11e9-a32f-2a2ae2dbcce4</n1:equipmentComponentUniqueIDReference>
			<n1:application>AHU</n1:application>
			<n1:motorType>Induction</n1:motorType>
			<n1:outputPower>15.00</n1:outputPower>
			<n1:speedControl>variable speed</n1:speedControl>
			<n1:speed>1765.00</n1:speed>
			<n1:frameSize>254T</n1:frameSize>
			<n1:enclosureType>TEFC</n1:enclosureType>
			<n1:serviceFactor>1.15</n1:serviceFactor>
			<n1:lockedRotorKVACode>H</n1:lockedRotorKVACode>
			<n1:NEMANominalEfficiency>92.6</n1:NEMANominalEfficiency>
			<n1:torqueCurrentCharacteristics>A</n1:torqueCurrentCharacteristics>
			<n1:duty>continuous</n1:duty>
			<n1:insulationClass>F</n1:insulationClass>
			<n1:maximumAmbientTemperature>104.00</n1:maximumAmbientTemperature>
		</n1:MotorPropertySet>
		<n1:PackagedUnitPropertySet>
			<n1:uniqueID>aadfd6ce-af03-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentUniqueIDReference>3465f460-ae40-11e9-a2a3-2a2ae2dbcce4</n1:equipmentComponentUniqueIDReference>
			<n1:refrigerantType>unknown</n1:refrigerantType>
			<n1:compressorType>reciprocating</n1:compressorType>
			<n1:IEER>15.00</n1:IEER>
			<n1:SEER>13.00</n1:SEER>
			<n1:EER>12.10</n1:EER>
			<n1:coolingCapacity>156.58</n1:coolingCapacity>
			<n1:HSPF>12.33</n1:HSPF>
			<n1:heatingCapacity>280.00</n1:heatingCapacity>
			<n1:heatingCOP>0.77</n1:heatingCOP>
			<n1:compressorControlMethod>DDC</n1:compressorControlMethod>
			<n1:fanPosition>draw through</n1:fanPosition>
		</n1:PackagedUnitPropertySet>
		<n1:PumpPropertySet>
			<n1:uniqueID>9251b450-af04-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:equipmentComponentUniqueIDReference>3465f5aa-ae40-11e9-a2a3-2a2ae2dbcce4</n1:equipmentComponentUniqueIDReference>
			<n1:pumpCapacity>170.00</n1:pumpCapacity>
			<n1:application>Heating</n1:application>
			<n1:pumpType>Centrifugal</n1:pumpType>
			<n1:configuration>In Line</n1:configuration>
			<n1:driveType>Direct</n1:driveType>
			<n1:casingMaterial>Cast Iron</n1:casingMaterial>
			<n1:impellerMaterial>Bronze</n1:impellerMaterial>
			<n1:shaftMaterial>Steel</n1:shaftMaterial>
			<n1:shaftSealType>Mechanical</n1:shaftSealType>
			<n1:PNRating>175.00</n1:PNRating>
			<n1:connectionType>flanged</n1:connectionType>
			<n1:impellerDiameter>7.90</n1:impellerDiameter>
			<n1:numberOfImpellers>1</n1:numberOfImpellers>
			<n1:suctionConnectionDiameter>2.50</n1:suctionConnectionDiameter>
			<n1:dischargeConnectionDiameter>2.00</n1:dischargeConnectionDiameter>
			<n1:ratedFlow>170.00</n1:ratedFlow>
			<n1:churnPressure>60.00</n1:churnPressure>
			<n1:controllerType>VFD</n1:controllerType>
			<n1:dischargeHead>55.00</n1:dischargeHead>
		</n1:PumpPropertySet>
	</n1:ExtendedPropertySets>
	<n1:MaintenanceTasks>
		<n1:MaintenanceTask>
			<n1:uniqueID>2cb8a224-d980-11e9-8a34-2a2ae2dbcce4</n1:uniqueID>
			<n1:maintenanceTaskName>Test Boiler Water</n1:maintenanceTaskName>
			<n1:equipmentTypeUniqueIDReference>d7a65520-ad87-11e9-a2a3-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:inspectionTask>Perform chemical testing of system water.</n1:inspectionTask>
			<n1:maintenanceTask>Verify water treatment target levels are being maintained.</n1:maintenanceTask>
			<n1:recommendedCorrectiveAction>Repair equipment, and treat as needed to ensure proper water chemistry.</n1:recommendedCorrectiveAction>
			<n1:maintenanceType>routine</n1:maintenanceType>
			<n1:technicianCategory>any</n1:technicianCategory>
			<n1:requiredTime>0.50</n1:requiredTime>
			<n1:requiredTools>water test kit</n1:requiredTools>
			<n1:requiredSupplies>water treatment kit</n1:requiredSupplies>
			<n1:serviceCartType>boiler</n1:serviceCartType>
			<n1:frequency>monthly</n1:frequency>
			<n1:overhaulBasis>failure to maintain target levels</n1:overhaulBasis>
		</n1:MaintenanceTask>
		<n1:MaintenanceTask>
			<n1:uniqueID>2cb8a4a4-d980-11e9-8a34-2a2ae2dbcce4</n1:uniqueID>
			<n1:maintenanceTaskName>Check Control System Data Points</n1:maintenanceTaskName>
			<n1:equipmentTypeUniqueIDReference>d7a65764-ad87-11e9-a2a3-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:inspectionTask>Check set points, trended points, and time schedules.</n1:inspectionTask>
			<n1:maintenanceTask>Note and respond as required.</n1:maintenanceTask>
			<n1:recommendedCorrectiveAction>Repair or replace components as needed to ensure proper operation.</n1:recommendedCorrectiveAction>
			<n1:maintenanceType>routine</n1:maintenanceType>
			<n1:technicianCategory>Control System Operator</n1:technicianCategory>
			<n1:requiredTime>20.00</n1:requiredTime>
			<n1:requiredTools>none</n1:requiredTools>
			<n1:requiredSupplies>none</n1:requiredSupplies>
			<n1:serviceCartType>none</n1:serviceCartType>
			<n1:frequency>semiannual</n1:frequency>
			<n1:overhaulBasis>failure to operate properly</n1:overhaulBasis>
		</n1:MaintenanceTask>
		<n1:MaintenanceTask>
			<n1:uniqueID>2cb8a602-d980-11e9-8a34-2a2ae2dbcce4</n1:uniqueID>
			<n1:maintenanceTaskName>Check ERU Dampers</n1:maintenanceTaskName>
			<n1:equipmentTypeUniqueIDReference>d7a65ad4-ad87-11e9-a2a3-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:inspectionTask>Check dampers for condition, setting, and operation.</n1:inspectionTask>
			<n1:maintenanceTask>Clean, lubricate, and verify proper operation.</n1:maintenanceTask>
			<n1:recommendedCorrectiveAction>Repair or replace as needed to ensure proper operation.</n1:recommendedCorrectiveAction>
			<n1:maintenanceType>routine</n1:maintenanceType>
			<n1:technicianCategory>HVAC Technician</n1:technicianCategory>
			<n1:requiredTime>5.00</n1:requiredTime>
			<n1:requiredTools>basic</n1:requiredTools>
			<n1:requiredSupplies>lubricant</n1:requiredSupplies>
			<n1:serviceCartType>basic</n1:serviceCartType>
			<n1:frequency>semiannual</n1:frequency>
			<n1:overhaulBasis>failure to operate properly</n1:overhaulBasis>
		</n1:MaintenanceTask>
		<n1:MaintenanceTask>
			<n1:uniqueID>2cb8a828-d980-11e9-8a34-2a2ae2dbcce4</n1:uniqueID>
			<n1:maintenanceTaskName>Check Unit Operation</n1:maintenanceTaskName>
			<n1:equipmentTypeUniqueIDReference>d7a65c28-ad87-11e9-a2a3-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:inspectionTask>Check control system and devices for evidence of improper operation.</n1:inspectionTask>
			<n1:maintenanceTask>Clean, lubricate, adjust.</n1:maintenanceTask>
			<n1:recommendedCorrectiveAction>Repair or replace components as needed to ensure proper operation.</n1:recommendedCorrectiveAction>
			<n1:maintenanceType>routine</n1:maintenanceType>
			<n1:technicianCategory>HVAC Technician</n1:technicianCategory>
			<n1:requiredTime>3.00</n1:requiredTime>
			<n1:requiredTools>HVAC kit</n1:requiredTools>
			<n1:requiredSupplies>lubricant</n1:requiredSupplies>
			<n1:serviceCartType>HVAC</n1:serviceCartType>
			<n1:frequency>semiannual</n1:frequency>
			<n1:overhaulBasis>failure to operate properly</n1:overhaulBasis>
		</n1:MaintenanceTask>
		<n1:MaintenanceTask>
			<n1:uniqueID>2cb8ab7a-d980-11e9-8a34-2a2ae2dbcce4</n1:uniqueID>
			<n1:maintenanceTaskName>Inspect Pump</n1:maintenanceTaskName>
			<n1:equipmentTypeUniqueIDReference>d7a65d5e-ad87-11e9-a2a3-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:inspectionTask>Inspect pumps and associated electrical components.</n1:inspectionTask>
			<n1:maintenanceTask>Clean, and verify proper operation.</n1:maintenanceTask>
			<n1:recommendedCorrectiveAction>Repair or replace as needed to ensure proper operation.</n1:recommendedCorrectiveAction>
			<n1:maintenanceType>routine</n1:maintenanceType>
			<n1:technicianCategory>HVAC Technician</n1:technicianCategory>
			<n1:requiredTime>0.50</n1:requiredTime>
			<n1:requiredTools>Pump kit</n1:requiredTools>
			<n1:requiredSupplies>none</n1:requiredSupplies>
			<n1:serviceCartType>Pump</n1:serviceCartType>
			<n1:frequency>semiannual</n1:frequency>
			<n1:overhaulBasis>failure to operate properly</n1:overhaulBasis>
		</n1:MaintenanceTask>
		<n1:MaintenanceTask>
			<n1:uniqueID>e1687574-badf-11e9-a2a3-2a2ae2dbcce4</n1:uniqueID>
			<n1:maintenanceTaskName>Check AirHandler Filters</n1:maintenanceTaskName>
			<n1:equipmentTypeUniqueIDReference>c3e652c2-b310-11e9-a2a3-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:inspectionTask>Check for particulate accumulation on filters.</n1:inspectionTask>
			<n1:maintenanceTask>Clean or replace as needed to ensure proper operation.</n1:maintenanceTask>
			<n1:recommendedCorrectiveAction>Evaluate frequency of change requirement.</n1:recommendedCorrectiveAction>
			<n1:maintenanceType>routine</n1:maintenanceType>
			<n1:technicianCategory>HVAC Technician</n1:technicianCategory>
			<n1:requiredTime>0.25</n1:requiredTime>
			<n1:requiredTools>screwdriver, flashlight</n1:requiredTools>
			<n1:requiredSupplies>replacement filters</n1:requiredSupplies>
			<n1:serviceCartType>none</n1:serviceCartType>
			<n1:frequency>quarterly</n1:frequency>
			<n1:overhaulBasis>inspection</n1:overhaulBasis>
		</n1:MaintenanceTask>
		<n1:MaintenanceTask>
			<n1:uniqueID>2cb8ace2-d980-11e9-8a34-2a2ae2dbcce4</n1:uniqueID>
			<n1:maintenanceTaskName>Check Coil Refrigerant</n1:maintenanceTaskName>
			<n1:equipmentTypeUniqueIDReference>c3e6575e-b310-11e9-a2a3-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:inspectionTask>Check refrigerant system temperatures.</n1:inspectionTask>
			<n1:maintenanceTask>When outside of recommended levels, find and record location of identified leaks.</n1:maintenanceTask>
			<n1:recommendedCorrectiveAction>Repair, and adjust refrigerant to achieve optimal operating levels.</n1:recommendedCorrectiveAction>
			<n1:maintenanceType>routine</n1:maintenanceType>
			<n1:technicianCategory>HVAC Technician</n1:technicianCategory>
			<n1:requiredTime>0.50</n1:requiredTime>
			<n1:requiredTools>HVAC kit</n1:requiredTools>
			<n1:requiredSupplies>coil fluids</n1:requiredSupplies>
			<n1:serviceCartType>HVAC</n1:serviceCartType>
			<n1:frequency>annual</n1:frequency>
			<n1:overhaulBasis>leaking</n1:overhaulBasis>
		</n1:MaintenanceTask>
		<n1:MaintenanceTask>
			<n1:uniqueID>2cb8ae22-d980-11e9-8a34-2a2ae2dbcce4</n1:uniqueID>
			<n1:maintenanceTaskName>Check Coil Fluid Flow</n1:maintenanceTaskName>
			<n1:equipmentTypeUniqueIDReference>c3e6598e-b310-11e9-a2a3-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:inspectionTask>Check for proper fluid flow and for fluid leaks.</n1:inspectionTask>
			<n1:maintenanceTask>Adjust flow when outside of recommended flow range. When leaking, find and record the location of identified leaks.</n1:maintenanceTask>
			<n1:recommendedCorrectiveAction>Repair and adjust to achieve optimal operating flows.</n1:recommendedCorrectiveAction>
			<n1:maintenanceType>routine</n1:maintenanceType>
			<n1:technicianCategory>HVAC Technician</n1:technicianCategory>
			<n1:requiredTime>0.50</n1:requiredTime>
			<n1:requiredTools>HVAC kit</n1:requiredTools>
			<n1:requiredSupplies>coil fluids</n1:requiredSupplies>
			<n1:serviceCartType>HVAC</n1:serviceCartType>
			<n1:frequency>annual</n1:frequency>
			<n1:overhaulBasis>leaking</n1:overhaulBasis>
		</n1:MaintenanceTask>
		<n1:MaintenanceTask>
			<n1:uniqueID>2cb8af58-d980-11e9-8a34-2a2ae2dbcce4</n1:uniqueID>
			<n1:maintenanceTaskName>Check Coil Biology</n1:maintenanceTaskName>
			<n1:equipmentTypeUniqueIDReference>7bf3199e-cc1c-11e9-a32f-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:inspectionTask>Check drain pan, drain line, coil, and other areas of moisture accumulation for visible signs of biological growth.</n1:inspectionTask>
			<n1:maintenanceTask>Clean, and verify proper operation.</n1:maintenanceTask>
			<n1:recommendedCorrectiveAction>Disinfect as needed.</n1:recommendedCorrectiveAction>
			<n1:maintenanceType>routine</n1:maintenanceType>
			<n1:technicianCategory>HVAC Technician</n1:technicianCategory>
			<n1:requiredTime>0.30</n1:requiredTime>
			<n1:requiredTools>HVAC kit</n1:requiredTools>
			<n1:requiredSupplies>disinfectant</n1:requiredSupplies>
			<n1:serviceCartType>HVAC</n1:serviceCartType>
			<n1:frequency>annual</n1:frequency>
			<n1:overhaulBasis>n/a</n1:overhaulBasis>
		</n1:MaintenanceTask>
		<n1:MaintenanceTask>
			<n1:uniqueID>2cb8b0de-d980-11e9-8a34-2a2ae2dbcce4</n1:uniqueID>
			<n1:maintenanceTaskName>Check Fan Blades</n1:maintenanceTaskName>
			<n1:equipmentTypeUniqueIDReference>c3e65be6-b310-11e9-a2a3-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:inspectionTask>Check fan blades and fan housing.</n1:inspectionTask>
			<n1:maintenanceTask>Clean as needed.</n1:maintenanceTask>
			<n1:recommendedCorrectiveAction>Repair or replace as needed to ensure proper operation.</n1:recommendedCorrectiveAction>
			<n1:maintenanceType>routine</n1:maintenanceType>
			<n1:technicianCategory>HVAC Technician</n1:technicianCategory>
			<n1:requiredTime>0.30</n1:requiredTime>
			<n1:requiredTools>HVAC kit</n1:requiredTools>
			<n1:requiredSupplies>cleaning fluid</n1:requiredSupplies>
			<n1:serviceCartType>HVAC</n1:serviceCartType>
			<n1:frequency>annual</n1:frequency>
			<n1:overhaulBasis>n/a</n1:overhaulBasis>
		</n1:MaintenanceTask>
		<n1:MaintenanceTask>
			<n1:uniqueID>2cb8b228-d980-11e9-8a34-2a2ae2dbcce4</n1:uniqueID>
			<n1:maintenanceTaskName>Check Fan Controls</n1:maintenanceTaskName>
			<n1:equipmentTypeUniqueIDReference>7bf31ea8-cc1c-11e9-a32f-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:inspectionTask>Check control box for dirt, debris, and/or loose terminations.</n1:inspectionTask>
			<n1:maintenanceTask>Clean and tighten electrical connections as needed.</n1:maintenanceTask>
			<n1:recommendedCorrectiveAction>Repair, replace, or restore as needed to ensure proper operation.</n1:recommendedCorrectiveAction>
			<n1:maintenanceType>routine</n1:maintenanceType>
			<n1:technicianCategory>HVAC Technician</n1:technicianCategory>
			<n1:requiredTime>0.50</n1:requiredTime>
			<n1:requiredTools>HVAC kit</n1:requiredTools>
			<n1:requiredSupplies>cleaning fluid</n1:requiredSupplies>
			<n1:serviceCartType>HVAC</n1:serviceCartType>
			<n1:frequency>annual</n1:frequency>
			<n1:overhaulBasis>n/a</n1:overhaulBasis>
		</n1:MaintenanceTask>
		<n1:MaintenanceTask>
			<n1:uniqueID>2cb8b62e-d980-11e9-8a34-2a2ae2dbcce4</n1:uniqueID>
			<n1:maintenanceTaskName>Check Motor VFD</n1:maintenanceTaskName>
			<n1:equipmentTypeUniqueIDReference>c3e65d30-b310-11e9-a2a3-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:inspectionTask>Check variable-frequency drive for proper operation.</n1:inspectionTask>
			<n1:maintenanceTask>Correct as needed. Clean housing, and tighten connections as needed. Clean or replace air filter.</n1:maintenanceTask>
			<n1:recommendedCorrectiveAction>Repair, replace, or restore as needed to ensure proper operation.</n1:recommendedCorrectiveAction>
			<n1:maintenanceType>routine</n1:maintenanceType>
			<n1:technicianCategory>HVAC Technician</n1:technicianCategory>
			<n1:requiredTime>0.50</n1:requiredTime>
			<n1:requiredTools>HVAC kit</n1:requiredTools>
			<n1:requiredSupplies>cleaning fluid</n1:requiredSupplies>
			<n1:serviceCartType>HVAC</n1:serviceCartType>
			<n1:frequency>annual</n1:frequency>
			<n1:overhaulBasis>n/a</n1:overhaulBasis>
		</n1:MaintenanceTask>
		<n1:MaintenanceTask>
			<n1:uniqueID>2cb8b782-d980-11e9-8a34-2a2ae2dbcce4</n1:uniqueID>
			<n1:maintenanceTaskName>Check Motor Contactor</n1:maintenanceTaskName>
			<n1:equipmentTypeUniqueIDReference>7bf32308-cc1c-11e9-a32f-2a2ae2dbcce4</n1:equipmentTypeUniqueIDReference>
			<n1:inspectionTask>Check motor contactor for pitting or other signs of damage.</n1:inspectionTask>
			<n1:maintenanceTask>Clean and tighten electrical connections as needed.</n1:maintenanceTask>
			<n1:recommendedCorrectiveAction>Repair, replace, or restore as needed to ensure proper operation.</n1:recommendedCorrectiveAction>
			<n1:maintenanceType>routine</n1:maintenanceType>
			<n1:technicianCategory>HVAC Technician</n1:technicianCategory>
			<n1:requiredTime>0.25</n1:requiredTime>
			<n1:requiredTools>screwdriver, flashlight</n1:requiredTools>
			<n1:requiredSupplies>none</n1:requiredSupplies>
			<n1:serviceCartType>HVAC</n1:serviceCartType>
			<n1:frequency>annual</n1:frequency>
			<n1:overhaulBasis>n/a</n1:overhaulBasis>
		</n1:MaintenanceTask>
	</n1:MaintenanceTasks>
</n1:AssetOMDocumentation>