Table of Contents

Program Version:EnergyPlus, Version 8.7.0-78a111df4a, YMD=2024.07.07 15:37

Tabular Output Report in Format: HTML

Building: Ref Bldg Small Office New2004_v1.3_5.0

Environment: Miami Intl Ap FL USA TMY3 WMO#=722020

Simulation Timestamp: 2024-07-07 15:38:44


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-07-07 15:38:44

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 294.35 575.85 575.85
Net Site Energy 294.35 575.85 575.85
Total Source Energy 953.09 1864.57 1864.57
Net Source Energy 953.09 1864.57 1864.57


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.317
Natural Gas 1.092
District Cooling 0.794
District Heating 1.647
Steam 0.585
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 511.16
Net Conditioned Building Area 511.16
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 0.27 0.00 0.00 0.00 0.00
Cooling 69.71 0.00 0.00 0.00 0.00 0.00
Interior Lighting 56.31 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 36.24 0.00 0.00 0.00 0.00 0.00
Interior Equipment 87.61 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 34.02 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 10.19 0.00 0.00 0.00 17.59
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 283.89 10.46 0.00 0.00 0.00 17.59
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.27 0.00 0.00 0.00 0.00
Cooling General 69.71 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 56.31 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior Facade Lighting 36.24 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 87.61 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Fan Energy 34.02 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 10.19 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 17.59
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 181.05 0.00 0.00 0.00 0.00 0.00
HVAC 202.93 20.46 0.00 0.00 0.00 0.03
Other 171.40 0.00 0.00 0.00 0.00 0.00
Total 555.39 20.46 0.00 0.00 0.00 0.03


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 181.05 0.00 0.00 0.00 0.00 0.00
HVAC 202.93 20.46 0.00 0.00 0.00 0.03
Other 171.40 0.00 0.00 0.00 0.00 0.00
Total 555.39 20.46 0.00 0.00 0.00 0.03


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 283.891 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 283.891 100.00
     
Total On-Site and Utility Electric Sources 283.891 100.00
Total Electricity End Uses 283.891 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 17.59 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 17.59 100.00
Total Water End Uses 17.59 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 114.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 693.17


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

Tariff Report

| FPL_GSLD-1_GENERALSERVICELARGEDEMAND | FPL_GSD-1_GENERALSERVICEDEMAND | FPL_GS-1_NONDEMAND | FL_EIAMONTHLYRATEGAS |

Economics Results Summary Report

| Entire Facility |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-07-07 15:38:44

General

Value
Program Version and Build EnergyPlus, Version 8.7.0-78a111df4a, YMD=2024.07.07 15:37
RunPeriod Miami Intl Ap FL USA TMY3 WMO#=722020
Weather File Miami Intl Ap FL USA TMY3 WMO#=722020
Latitude [deg] 25.82
Longitude [deg] -80.3
Elevation [m] 11.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.68 16.73 11.16 20.64 11.16
Gross Window-Wall Ratio [%] 21.20 19.81 19.81 24.44 19.81
Above Ground Window-Wall Ratio [%] 21.20 19.81 19.81 24.44 19.81


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.68 16.73 11.16 20.64 11.16
Gross Window-Wall Ratio [%] 21.20 19.81 19.81 24.44 19.81
Above Ground Window-Wall Ratio [%] 21.20 19.81 19.81 24.44 19.81


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 598.76
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
ATTIC 567.98 No No 720.19 1.00 0.00 0.00 0.00 0.00      
CORE_ZN 149.66 Yes Yes 456.46 1.00 0.00 0.00 0.00 0.00 10.7600 18.58 10.7600
PERIMETER_ZN_1 113.45 Yes Yes 346.02 1.00 84.45 0.00 20.64 20.64 10.7600 18.58 10.7600
PERIMETER_ZN_2 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.16 11.16 10.7600 18.58 10.7600
PERIMETER_ZN_3 113.45 Yes Yes 346.02 1.00 84.45 0.00 16.73 16.73 10.7600 18.58 10.7600
PERIMETER_ZN_4 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.16 11.16 10.7600 18.58 10.7600
Total 511.16     1559.03   281.51 0.00 59.68 59.68 10.7600 18.58 10.7600
Conditioned Total 511.16     1559.03   281.51 0.00 59.68 59.68 10.7600 18.58 10.7600
Unconditioned Total 567.98     720.19   0.00 0.00 0.00 0.00 0.0000   0.0000
Not Part of Total 567.98     720.19   0.00 0.00 0.00 0.00 0.0000   0.0000



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-07 15:38:44

End Uses

Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 08-JUN-15:50 15-DEC-07:10 - - - 16-JAN-12:50
Heating 0.00 5917.20 0.00 0.00 0.00 0.00
Cooling 7346.50 0.00 0.00 0.00 0.00 0.00
Interior Lighting 5500.05 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 4950.05 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1724.56 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 20.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 19521.16 5937.20 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Propane [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 5917.20 0.00 0.00 0.00 0.00
Cooling General 7346.50 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 5500.05 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior Facade Lighting 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 4950.05 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Fan Energy 1724.56 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 20.00 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-07-07 15:38:44

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Additional Fuel [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 0.29 0.00 0.00 0.00
Cooling 231.23 0.00 0.00 0.00 0.00
Interior Lighting 186.78 0.00 0.00 0.00 0.00
Exterior Lighting 120.20 0.00 0.00 0.00 0.00
Interior Equipment 290.62 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 112.84 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 11.13 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 941.67 11.42 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.57 0.00 0.00 0.00
Cooling 452.37 0.00 0.00 0.00 0.00
Interior Lighting 365.40 0.00 0.00 0.00 0.00
Exterior Lighting 235.15 0.00 0.00 0.00 0.00
Interior Equipment 568.54 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 220.76 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 21.77 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1842.23 22.34 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Additional Fuel [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.57 0.00 0.00 0.00
Cooling 452.37 0.00 0.00 0.00 0.00
Interior Lighting 365.40 0.00 0.00 0.00 0.00
Exterior Lighting 235.15 0.00 0.00 0.00 0.00
Interior Equipment 568.54 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 220.76 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 21.77 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1842.23 22.34 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-07-07 15:38:44

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
MIAMI ANN HTG 99.6% CONDNS DB 8.00 0.00 8.00 Wetbulb [C] 4.40 340.00
MIAMI ANN CLG .4% CONDNS WB=>MDB 30.50 6.70 26.70 Wetbulb [C] 4.70 140.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-07-07 15:38:44

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
ATTIC_SOFFIT_EAST ATTIC NON-RES FLOOR 0.08 0.195 0.203 11.44 11.44 45.00 180.00  
ATTIC_SOFFIT_NORTH ATTIC NON-RES FLOOR 0.08 0.195 0.203 16.97 16.97 315.00 180.00  
ATTIC_SOFFIT_SOUTH ATTIC NON-RES FLOOR 0.08 0.195 0.203 16.97 16.97 225.00 180.00  
ATTIC_SOFFIT_WEST ATTIC NON-RES FLOOR 0.08 0.195 0.203 11.44 11.44 270.00 180.00  
ATTIC_ROOF_EAST ATTIC NON-RES ROOF 0.30 5.082 16.833 101.87 101.87 90.00 18.45  
ATTIC_ROOF_NORTH ATTIC NON-RES ROOF 0.30 5.082 16.833 197.51 197.51 0.00 18.45  
ATTIC_ROOF_SOUTH ATTIC NON-RES ROOF 0.30 5.082 16.833 197.51 197.51 180.00 18.45  
ATTIC_ROOF_WEST ATTIC NON-RES ROOF 0.30 5.082 16.833 101.87 101.87 270.00 18.45  
CORE_ZN_FLOOR EXT-SLAB 0.30 2.193 3.401 149.66 149.66 270.00 180.00  
PERIMETER_ZN_1_WALL_SOUTH MASS NON-RES EXT WALL 0.08 2.377 3.691 84.45 63.82 180.00 90.00 S
PERIMETER_ZN_1_FLOOR EXT-SLAB 0.30 2.193 3.401 113.45 113.45 135.00 180.00  
PERIMETER_ZN_2_WALL_EAST MASS NON-RES EXT WALL 0.08 2.377 3.691 56.30 45.15 90.00 90.00 E
PERIMETER_ZN_2_FLOOR EXT-SLAB 0.30 2.193 3.401 67.30 67.30 270.00 180.00  
PERIMETER_ZN_3_WALL_NORTH MASS NON-RES EXT WALL 0.08 2.377 3.691 84.45 67.72 0.00 90.00 N
PERIMETER_ZN_3_FLOOR EXT-SLAB 0.30 2.193 3.401 113.45 113.45 180.00 180.00  
PERIMETER_ZN_4_WALL_WEST MASS NON-RES EXT WALL 0.08 2.377 3.691 56.30 45.15 270.00 90.00 W
PERIMETER_ZN_4_FLOOR EXT-SLAB 0.30 2.193 3.401 67.30 67.30 90.00 180.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 WINDOW NON-RES FIXED 2.79 0.00 0.00 2.79 2.79 5.835 0.251 0.110     No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 WINDOW NON-RES FIXED 2.79 0.00 0.00 2.79 2.79 5.835 0.251 0.110     No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 WINDOW NON-RES FIXED 2.79 0.00 0.00 2.79 2.79 5.835 0.251 0.110     No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 WINDOW NON-RES FIXED 2.79 0.00 0.00 2.79 2.79 5.835 0.251 0.110     No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 WINDOW NON-RES FIXED 2.79 0.00 0.00 2.79 2.79 5.835 0.251 0.110     No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 WINDOW NON-RES FIXED 2.79 0.00 0.00 2.79 2.79 5.835 0.251 0.110     No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_DOOR WINDOW NON-RES FIXED 3.91 0.00 0.00 3.91 3.91 5.835 0.251 0.110     No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 WINDOW NON-RES FIXED 2.79 0.00 0.00 2.79 2.79 5.835 0.251 0.110     No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 WINDOW NON-RES FIXED 2.79 0.00 0.00 2.79 2.79 5.835 0.251 0.110     No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 WINDOW NON-RES FIXED 2.79 0.00 0.00 2.79 2.79 5.835 0.251 0.110     No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 WINDOW NON-RES FIXED 2.79 0.00 0.00 2.79 2.79 5.835 0.251 0.110     No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 WINDOW NON-RES FIXED 2.79 0.00 0.00 2.79 2.79 5.835 0.251 0.110     No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 WINDOW NON-RES FIXED 2.79 0.00 0.00 2.79 2.79 5.835 0.251 0.110     No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 WINDOW NON-RES FIXED 2.79 0.00 0.00 2.79 2.79 5.835 0.251 0.110     No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 WINDOW NON-RES FIXED 2.79 0.00 0.00 2.79 2.79 5.835 0.251 0.110     No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 WINDOW NON-RES FIXED 2.79 0.00 0.00 2.79 2.79 5.835 0.251 0.110     No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 WINDOW NON-RES FIXED 2.79 0.00 0.00 2.79 2.79 5.835 0.251 0.110     No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 WINDOW NON-RES FIXED 2.79 0.00 0.00 2.79 2.79 5.835 0.251 0.110     No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 WINDOW NON-RES FIXED 2.79 0.00 0.00 2.79 2.79 5.835 0.251 0.110     No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 WINDOW NON-RES FIXED 2.79 0.00 0.00 2.79 2.79 5.835 0.251 0.110     No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 WINDOW NON-RES FIXED 2.79 0.00 0.00 2.79 2.79 5.835 0.251 0.110     No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average           59.68 5.835 0.251 0.110              
North Total or Average           16.73 5.835 0.251 0.110              
Non-North Total or Average           42.95 5.835 0.251 0.110              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-07-07 15:38:44

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 0.57 0.58 0.58 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 0.57 0.58 0.58 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 0.57 0.58 0.58 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 0.57 0.58 0.58 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 0.57 0.58 0.58 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 0.58 0.58 0.58 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_DOOR 0.83 0.84 0.84 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.04 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 0.00 0.00 0.00 0.05 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 0.00 0.00 0.86 0.00 0.00 0.76 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 0.00 0.00 0.86 0.00 0.00 0.76 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 0.00 0.00 0.86 0.00 0.00 0.76 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 0.00 0.00 0.86 0.00 0.00 0.76 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-07-07 15:38:44

Interior Lighting

Zone Lighting Power Density [W/m2] Zone Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORE_ZN_LIGHTS CORE_ZN 10.7600 149.66 1610.31 General ZONE_LIGHT_SCH_CORE_ZN 0.00 68.09 68.09 0.0000 Y 20.58
PERIMETER_ZN_1_LIGHTS PERIMETER_ZN_1 10.7600 113.45 1220.72 General ZONE_LIGHT_SCH_PERIMETER_ZN_1 0.00 35.39 35.39 0.0000 Y 8.11
PERIMETER_ZN_2_LIGHTS PERIMETER_ZN_2 10.7600 67.30 724.15 General ZONE_LIGHT_SCH_PERIMETER_ZN_2 0.00 54.61 54.61 0.0000 Y 7.42
PERIMETER_ZN_3_LIGHTS PERIMETER_ZN_3 10.7600 113.45 1220.72 General ZONE_LIGHT_SCH_PERIMETER_ZN_3 0.00 50.81 50.81 0.0000 Y 11.64
PERIMETER_ZN_4_LIGHTS PERIMETER_ZN_4 10.7600 67.30 724.15 General ZONE_LIGHT_SCH_PERIMETER_ZN_4 0.00 62.92 62.92 0.0000 Y 8.55
Interior Lighting Total   10.7600 511.16 5500.05               56.31


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
CORE_ZN_DAYLREFPT1 CORE_ZN CORE_ZN_DAYLCTRL SplitFlux Continuous 1.00 1610.31 1610.31
PERIMETER_ZN_1_DAYLREFPT1 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous 1.00 1220.72 1220.72
PERIMETER_ZN_2_DAYLREFPT1 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous 1.00 724.15 724.15
PERIMETER_ZN_3_DAYLREFPT1 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous 1.00 1220.72 1220.72
PERIMETER_ZN_4_DAYLREFPT1 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous 1.00 724.15 724.15


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 2303.00 AstronomicalClock -   83.82 83.82 36.24
Exterior Lighting Total 2303.00           36.24



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-07-07 15:38:44

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PSZ-AC:1_COOLC DXCOIL Coil:Cooling:DX:SingleSpeed   7229.45 4887.71 2341.74 0.68 3.67    
PSZ-AC:2_COOLC DXCOIL Coil:Cooling:DX:SingleSpeed   6734.44 4553.04 2181.40 0.68 3.67    
PSZ-AC:3_COOLC DXCOIL Coil:Cooling:DX:SingleSpeed   6100.96 4461.54 1639.42 0.73 3.67    
PSZ-AC:4_COOLC DXCOIL Coil:Cooling:DX:SingleSpeed   6774.96 4718.67 2056.29 0.70 3.67    
PSZ-AC:5_COOLC DXCOIL Coil:Cooling:DX:SingleSpeed   6658.65 4865.60 1793.05 0.73 3.67    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
PSZ-AC:1_COOLC DXCOIL   7003.6 3.19 10.88 12.53 12.16
PSZ-AC:2_COOLC DXCOIL   6524.0 3.19 10.88 12.53 12.16
PSZ-AC:3_COOLC DXCOIL   5867.6 3.09 10.56 12.12 11.55
PSZ-AC:4_COOLC DXCOIL   6545.7 3.15 10.76 12.38 11.93
PSZ-AC:5_COOLC DXCOIL   6404.4 3.09 10.56 12.13 11.56
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PSZ-AC:1_COOLC DXCOIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:2_COOLC DXCOIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:3_COOLC DXCOIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:4_COOLC DXCOIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:5_COOLC DXCOIL Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
PSZ-AC:1_HEATC Coil:Heating:Fuel   7950.90 0.80
PSZ-AC:2_HEATC Coil:Heating:Fuel   7186.98 0.80
PSZ-AC:3_HEATC Coil:Heating:Fuel   7481.71 0.80
PSZ-AC:4_HEATC Coil:Heating:Fuel   7746.03 0.80
PSZ-AC:5_HEATC Coil:Heating:Fuel   8099.35 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
PSZ-AC:1_FAN Fan:ConstantVolume 0.54 622.00 0.29 337.68 1159.91 1.00 Fan Energy
PSZ-AC:2_FAN Fan:ConstantVolume 0.54 622.00 0.27 314.56 1159.91 1.00 Fan Energy
PSZ-AC:3_FAN Fan:ConstantVolume 0.54 622.00 0.30 349.16 1159.91 1.00 Fan Energy
PSZ-AC:4_FAN Fan:ConstantVolume 0.54 622.00 0.30 342.80 1159.91 1.00 Fan Energy
PSZ-AC:5_FAN Fan:ConstantVolume 0.54 622.00 0.33 380.36 1159.91 1.00 Fan Energy


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 0.00 0.000003 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.15 845000.00 0.80 4.58 0.57



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-07-07 15:38:44

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 3150.60 3780.72 25.26 0.243 0.291 MIAMI ANN CLG .4% CONDNS WB=>MDB 7/21 07:00:00 24.00 24.00 0.01067 24.40 0.01936 0.081 0.00
PERIMETER_ZN_1 2774.01 3328.82 29.34 0.226 0.271 MIAMI ANN CLG .4% CONDNS WB=>MDB 7/21 16:50:00 24.00 24.00 0.00925 29.65 0.02067 0.061 0.00
PERIMETER_ZN_2 3079.20 3695.04 54.90 0.251 0.301 MIAMI ANN CLG .4% CONDNS WB=>MDB 7/21 09:20:00 24.00 24.00 0.00893 27.19 0.02067 0.036 0.00
PERIMETER_ZN_3 3022.59 3627.11 31.97 0.246 0.296 MIAMI ANN CLG .4% CONDNS WB=>MDB 7/21 07:20:00 24.00 24.00 0.00958 24.78 0.01982 0.061 0.00
PERIMETER_ZN_4 3354.29 4025.14 59.81 0.273 0.328 MIAMI ANN CLG .4% CONDNS WB=>MDB 7/21 17:40:00 24.00 24.00 0.00889 29.12 0.02067 0.036 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 1040.07 1248.08 8.34 0.045 0.081 MIAMI ANN HTG 99.6% CONDNS DB 1/21 06:00:00 21.00 21.00 0.00731 8.00 0.00666 0.081 0.00
PERIMETER_ZN_1 2598.08 3117.70 27.48 0.111 0.134 MIAMI ANN HTG 99.6% CONDNS DB 1/21 06:00:00 21.00 21.00 0.00774 8.00 0.00666 0.061 0.00
PERIMETER_ZN_2 1693.85 2032.62 30.20 0.073 0.087 MIAMI ANN HTG 99.6% CONDNS DB 1/21 06:00:00 21.00 21.00 0.00774 8.00 0.00666 0.036 0.00
PERIMETER_ZN_3 2486.77 2984.13 26.30 0.107 0.128 MIAMI ANN HTG 99.6% CONDNS DB 1/21 06:00:00 21.00 21.00 0.00773 8.00 0.00666 0.061 0.00
PERIMETER_ZN_4 1688.90 2026.68 30.11 0.072 0.087 MIAMI ANN HTG 99.6% CONDNS DB 1/21 06:00:00 21.00 21.00 0.00774 8.00 0.00666 0.036 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
PSZ-AC:1 0.29 0.29 0.08 0.08
PSZ-AC:2 0.27 0.27 0.13 0.13
PSZ-AC:3 0.30 0.30 0.09 0.09
PSZ-AC:4 0.30 0.30 0.13 0.13
PSZ-AC:5 0.33 0.33 0.09 0.09


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-07-07 15:38:44

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORE_ZN 3985.00 929.33 635.67
PERIMETER_ZN_1 4275.33 420.83 199.83
PERIMETER_ZN_2 4189.33 620.00 240.00
PERIMETER_ZN_3 3856.50 910.17 294.17
PERIMETER_ZN_4 4156.83 646.33 228.00
ATTIC 0.00 0.00 0.00
Facility 4443.67 1338.00 693.17
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORE_ZN 0.00 80.17 0.00 39.17
PERIMETER_ZN_1 0.00 205.83 0.00 74.83
PERIMETER_ZN_2 0.00 254.50 0.00 35.17
PERIMETER_ZN_3 0.00 114.50 0.00 32.83
PERIMETER_ZN_4 0.00 278.33 0.00 33.67
ATTIC 0.00 0.00 0.00 0.00
Facility 0.00 699.50 0.00 114.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-07-07 15:38:44

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 3.85 8.05 456.46 0.546 0.117 0.000 0.000
PERIMETER_ZN_1 2.92 6.11 346.02 0.545 0.086 0.000 0.000
PERIMETER_ZN_2 1.73 3.62 205.26 0.545 0.097 0.000 0.000
PERIMETER_ZN_3 2.92 6.11 346.02 0.545 0.086 0.000 0.000
PERIMETER_ZN_4 1.73 3.62 205.26 0.545 0.097 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 3.85 8.05 456.46 0.000 0.003 0.000 0.000
PERIMETER_ZN_1 2.92 6.11 346.02 0.000 0.002 0.000 0.000
PERIMETER_ZN_2 1.73 3.62 205.26 0.000 0.002 0.000 0.000
PERIMETER_ZN_3 2.92 6.11 346.02 0.000 0.002 0.000 0.000
PERIMETER_ZN_4 1.73 3.62 205.26 0.000 0.002 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-07-07 15:38:44

Surfaces by Class

Total Outdoors
Wall 20 4
Floor 14 9
Roof 9 4
Internal Mass 5 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 21 21
Door 0 0
Glass Door 1 1
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 5
Conditioned Zones 5
Unconditioned Zones 1
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 521
Defaulted Fields 72
Fields with Defaults 947
Autosized Fields 65
Autosizable Fields 67
Autocalculated Fields 88
Autocalculatable Fields 152



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-07-07 15:38:44

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 283.89 1650.02 01-JAN-07:20 19521.16 08-JUN-15:50
Electricity:Building 143.92 1650.02 01-JAN-00:10 10450.10 04-JAN-10:00
Electricity:Zone:CORE_ZN 46.23 483.09 01-JAN-00:10 3059.60 04-JAN-08:40
InteriorLights:Electricity 56.31 0.00 01-JAN-00:10 5500.05 04-JAN-10:00
InteriorLights:Electricity:Zone:CORE_ZN 20.58 0.00 01-JAN-00:10 1610.31 04-JAN-08:40
General:InteriorLights:Electricity 56.31 0.00 01-JAN-00:10 5500.05 04-JAN-10:00
Electricity:Zone:PERIMETER_ZN_1 27.56 366.22 01-JAN-00:10 2319.37 04-JAN-08:50
InteriorLights:Electricity:Zone:PERIMETER_ZN_1 8.11 0.00 01-JAN-00:10 1220.72 04-JAN-08:50
Electricity:Zone:PERIMETER_ZN_2 18.96 217.24 01-JAN-00:10 1375.88 04-JAN-09:50
InteriorLights:Electricity:Zone:PERIMETER_ZN_2 7.42 0.00 01-JAN-00:10 724.15 04-JAN-09:50
Electricity:Zone:PERIMETER_ZN_3 31.09 366.22 01-JAN-00:10 2319.37 04-JAN-08:40
InteriorLights:Electricity:Zone:PERIMETER_ZN_3 11.64 0.00 01-JAN-00:10 1220.72 04-JAN-08:40
Electricity:Zone:PERIMETER_ZN_4 20.09 217.24 01-JAN-00:10 1375.88 04-JAN-08:40
InteriorLights:Electricity:Zone:PERIMETER_ZN_4 8.55 0.00 01-JAN-00:10 724.15 04-JAN-08:40
InteriorEquipment:Electricity 87.61 1650.02 01-JAN-00:10 4950.05 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_ZN 25.65 483.09 01-JAN-00:10 1449.28 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 87.61 1650.02 01-JAN-00:10 4950.05 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 19.45 366.22 01-JAN-00:10 1098.65 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 11.54 217.24 01-JAN-00:10 651.73 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 19.45 366.22 01-JAN-00:10 1098.65 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 11.54 217.24 01-JAN-00:10 651.73 02-JAN-08:10
ElectricityPurchased:Facility 283.89 1650.02 01-JAN-07:20 19521.16 08-JUN-15:50
ElectricityPurchased:Plant 283.89 1650.02 01-JAN-07:20 19521.16 08-JUN-15:50
Cogeneration:ElectricityPurchased 283.89 1650.02 01-JAN-07:20 19521.16 08-JUN-15:50
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 283.89 1650.02 01-JAN-07:20 19521.16 08-JUN-15:50
ElectricityNet:Plant 283.89 1650.02 01-JAN-07:20 19521.16 08-JUN-15:50
Cogeneration:ElectricityNet 283.89 1650.02 01-JAN-07:20 19521.16 08-JUN-15:50
Electricity:HVAC 103.73 0.00 01-JAN-00:10 10035.71 27-JUL-15:50
Fans:Electricity 34.02 0.00 01-JAN-00:10 1724.56 02-JAN-09:30
Fan Energy:Fans:Electricity 34.02 0.00 01-JAN-00:10 1724.56 02-JAN-09:30
ExteriorLights:Electricity 36.24 0.00 01-JAN-07:20 2303.00 01-JAN-00:10
Exterior Facade Lighting:ExteriorLights:Electricity 36.24 0.00 01-JAN-07:20 2303.00 01-JAN-00:10
Cooling:Electricity 69.71 0.00 01-JAN-00:10 8311.15 27-JUL-15:50
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Gas

Gas Annual Value [GJ] Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Gas:Facility 10.46 20.00 01-JAN-00:10 5937.20 15-DEC-07:10
Gas:Plant 10.19 20.00 01-JAN-00:10 2618.89 18-JAN-12:30
WaterSystems:Gas 10.19 20.00 01-JAN-00:10 2618.89 18-JAN-12:30
Water Heater:WaterSystems:Gas 10.19 20.00 01-JAN-00:10 2618.89 18-JAN-12:30
Gas:HVAC 0.27 0.00 01-JAN-00:10 5917.20 15-DEC-07:10
Heating:Gas 0.27 0.00 01-JAN-00:10 5917.20 15-DEC-07:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 17.59 0.00 20-MAY-21:50 0.00 16-JAN-12:50
Water:Plant 17.59 0.00 20-MAY-21:50 0.00 16-JAN-12:50
WaterSystems:Water 17.59 0.00 20-MAY-21:50 0.00 16-JAN-12:50
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
MainsWater:Facility 17.59 0.00 20-MAY-21:50 0.00 16-JAN-12:50
MainsWater:Plant 17.59 0.00 20-MAY-21:50 0.00 16-JAN-12:50
WaterSystems:MainsWater 17.59 0.00 20-MAY-21:50 0.00 16-JAN-12:50
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:WaterSystems:Water 17.59 0.00 20-MAY-21:50 0.00 16-JAN-12:50
General:WaterSystems:MainsWater 17.59 0.00 20-MAY-21:50 0.00 16-JAN-12:50


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
CO2:Facility 50623.33 0.000 01-JAN-07:20 0.004 13-SEP-14:20
ElectricEmissions:CO2 50078.45 0.000 01-JAN-07:20 0.003 08-JUN-15:50
CO:Facility 65.00 0.000 01-JAN-08:20 0.000 13-SEP-14:20
ElectricEmissions:CO 64.59 0.000 01-JAN-08:20 0.000 08-JUN-15:50
CH4:Facility 134.06 0.000 01-JAN-08:20 0.000 08-JUN-15:50
ElectricEmissions:CH4 134.05 0.000 01-JAN-08:20 0.000 08-JUN-15:50
NOx:Facility 88.81 0.000 01-JAN-08:20 0.000 13-SEP-14:20
ElectricEmissions:NOx 88.32 0.000 01-JAN-08:20 0.000 08-JUN-15:50
N2O:Facility 0.95 0.000 01-JAN-08:20 0.000 13-SEP-14:20
ElectricEmissions:N2O 0.94 0.000 01-JAN-08:20 0.000 08-JUN-15:50
SO2:Facility 337.55 0.000 01-JAN-08:20 0.000 08-JUN-15:50
ElectricEmissions:SO2 337.55 0.000 01-JAN-08:20 0.000 08-JUN-15:50
PM:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
ElectricEmissions:PM 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
PM10:Facility 3.22 0.000 01-JAN-08:20 0.000 13-SEP-14:20
ElectricEmissions:PM10 3.19 0.000 01-JAN-08:20 0.000 08-JUN-15:50
PM2.5:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
ElectricEmissions:PM2.5 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
NH3:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
ElectricEmissions:NH3 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
NMVOC:Facility 3.20 0.000 01-JAN-08:20 0.000 13-SEP-14:20
ElectricEmissions:NMVOC 3.18 0.000 01-JAN-08:20 0.000 08-JUN-15:50
Hg:Facility 0.00 0.000 01-JAN-08:20 0.000 08-JUN-15:50
ElectricEmissions:Hg 0.00 0.000 01-JAN-08:20 0.000 08-JUN-15:50
Pb:Facility 0.00 0.000 01-JAN-08:20 0.000 08-JUN-15:50
ElectricEmissions:Pb 0.00 0.000 01-JAN-08:20 0.000 08-JUN-15:50
Nuclear High:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
ElectricEmissions:Nuclear High 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
NaturalGasEmissions:CO2 544.87 0.000 01-JAN-09:00 0.000 15-DEC-07:10
NaturalGasEmissions:CO 0.42 0.000 01-JAN-00:10 0.000 15-DEC-07:10
NaturalGasEmissions:CH4 0.01 0.000 01-JAN-09:00 0.000 15-DEC-07:10
NaturalGasEmissions:NOx 0.49 0.000 01-JAN-09:00 0.000 15-DEC-07:10
NaturalGasEmissions:N2O 0.01 0.000 01-JAN-09:00 0.000 15-DEC-07:10
NaturalGasEmissions:SO2 0.00 0.000 01-JAN-08:20 0.000 15-DEC-07:10
NaturalGasEmissions:PM 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
NaturalGasEmissions:PM10 0.04 0.000 01-JAN-00:10 0.000 15-DEC-07:10
NaturalGasEmissions:PM2.5 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
NaturalGasEmissions:NH3 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
NaturalGasEmissions:NMVOC 0.03 0.000 01-JAN-09:00 0.000 15-DEC-07:10
NaturalGasEmissions:Hg 0.00 0.000 01-JAN-08:20 0.000 15-DEC-07:10
NaturalGasEmissions:Pb 0.00 0.000 01-JAN-09:00 0.000 15-DEC-07:10
NaturalGasEmissions:Nuclear High 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
Carbon Equivalent:Facility 14722.59 0.000 01-JAN-07:20 0.001 13-SEP-14:20
CarbonEquivalentEmissions:Carbon Equivalent 14722.59 0.000 01-JAN-07:20 0.001 13-SEP-14:20


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Nuclear Low:Facility 0.000 0.000 01-JAN-00:10 0.000 01-JAN-00:10
ElectricEmissions:Nuclear Low 0.000 0.000 01-JAN-00:10 0.000 01-JAN-00:10
NaturalGasEmissions:Nuclear Low 0.000 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
WaterEnvironmentalFactors:Facility 41776.047 0.000 01-JAN-07:20 0.003 08-JUN-15:50
ElectricEmissions:WaterEnvironmentalFactors 41776.047 0.000 01-JAN-07:20 0.003 08-JUN-15:50
NaturalGasEmissions:WaterEnvironmentalFactors 0.000 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 1.15 6.74 22-JUL-00:50 139.05 18-JAN-12:20
PlantLoopHeatingDemand:Plant 1.15 6.74 22-JUL-00:50 139.05 18-JAN-12:20
WaterSystems:PlantLoopHeatingDemand 1.15 6.74 22-JUL-00:50 139.05 18-JAN-12:20
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Facility 463.14 6.74 22-JUL-00:30 51521.47 29-MAY-05:10
EnergyTransfer:Building 161.11 0.00 01-JAN-00:10 18210.71 11-JUN-05:10
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer 1.04 0.00 01-JAN-00:10 1946.16 05-FEB-06:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 160.07 0.00 01-JAN-00:10 18200.71 11-JUN-05:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:CORE_ZN 31.37 0.00 01-JAN-00:10 4467.43 08-MAY-05:20
Heating:EnergyTransfer:Zone:CORE_ZN 0.15 0.00 01-JAN-00:10 402.98 03-APR-05:10
Cooling:EnergyTransfer:Zone:CORE_ZN 31.22 0.00 01-JAN-00:10 4467.43 08-MAY-05:20
EnergyTransfer:Zone:PERIMETER_ZN_1 41.81 0.00 01-JAN-00:10 4955.09 04-DEC-14:30
Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 0.20 0.00 01-JAN-00:10 456.09 20-APR-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 41.61 0.00 01-JAN-00:10 4955.09 04-DEC-14:30
EnergyTransfer:Zone:PERIMETER_ZN_2 28.74 0.00 01-JAN-00:10 3624.87 04-JUN-08:30
Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 0.22 0.00 01-JAN-00:10 338.49 20-DEC-07:00
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 28.53 0.00 01-JAN-00:10 3624.87 04-JUN-08:30
EnergyTransfer:Zone:PERIMETER_ZN_3 31.34 0.00 01-JAN-00:10 4459.79 11-JUN-05:10
Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 0.21 0.00 01-JAN-00:10 972.35 05-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 31.13 0.00 01-JAN-00:10 4459.79 11-JUN-05:10
EnergyTransfer:Zone:PERIMETER_ZN_4 27.85 0.00 01-JAN-00:10 3519.36 16-MAY-16:00
Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 0.26 0.00 01-JAN-00:10 365.81 20-DEC-07:00
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 27.59 0.00 01-JAN-00:10 3519.36 16-MAY-16:00
EnergyTransfer:Plant 1.15 6.74 22-JUL-00:50 139.05 18-JAN-12:20
WaterSystems:EnergyTransfer 1.15 6.74 22-JUL-00:50 139.05 18-JAN-12:20
General:WaterSystems:EnergyTransfer 1.15 6.74 22-JUL-00:50 139.05 18-JAN-12:20
EnergyTransfer:HVAC 300.88 0.00 01-JAN-00:10 39007.77 29-MAY-05:10
CoolingCoils:EnergyTransfer 300.67 0.00 01-JAN-00:10 39007.77 29-MAY-05:10
HeatingCoils:EnergyTransfer 0.21 0.00 01-JAN-00:10 4733.76 15-DEC-07:10
Source:Facility 1894.76 10968.05 01-JAN-07:20 131210.56 13-SEP-14:20
ElectricEmissions:Source 941.67 5473.10 01-JAN-08:20 64751.70 08-JUN-15:50
PurchasedElectricEmissions:Source 941.67 5473.10 01-JAN-07:20 64751.70 08-JUN-15:50
SoldElectricEmissions:Source 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
NaturalGasEmissions:Source 11.42 21.84 01-JAN-08:20 6483.42 15-DEC-07:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-07-07 15:38:44

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORE_ZN 0.000 0.000 0.150 -31.215 0.000 0.000 4.800 20.581 25.652 0.000 0.000 0.952 0.000 0.000 0.000 0.000 -2.518 -18.402
PERIMETER_ZN_1 0.000 0.000 0.205 -41.608 0.000 0.000 3.634 8.110 19.446 19.227 0.000 0.494 0.000 0.000 -5.592 0.000 -1.526 -2.390
PERIMETER_ZN_2 0.000 0.000 0.216 -28.525 0.000 0.000 2.158 7.423 11.535 10.348 0.000 0.328 0.424 0.000 -2.934 0.000 -0.974 -0.000
PERIMETER_ZN_3 0.000 0.000 0.210 -31.128 0.000 0.000 3.647 11.642 19.446 8.161 0.000 0.504 0.000 0.000 -4.253 0.000 -1.323 -6.905
PERIMETER_ZN_4 0.000 0.000 0.263 -27.586 0.000 0.000 2.159 8.553 11.535 9.998 0.000 0.327 0.000 0.000 -3.164 0.000 -1.000 -1.085
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 5.682 33.328 0.000 0.000 0.000 -39.010 -0.000
Total Facility 0.000 0.000 1.044 -160.062 0.000 0.000 16.399 56.309 87.614 47.734 0.000 8.287 33.752 0.000 -15.943 0.000 -46.350 -28.783


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 02-APR-05:05 0.00 0.00 0.00 -5361.71 0.00 0.00 46.07 1610.31 644.13 0.00 0.00 0.00 3215.09 0.00 -0.00 0.00 -153.89 0.00
PERIMETER_ZN_1 09-DEC-15:32 0.00 0.00 0.00 -5455.12 0.00 0.00 0.00 1220.72 366.22 2281.17 0.00 0.00 1650.06 0.00 -0.00 0.00 -63.05 0.00
PERIMETER_ZN_2 04-JUL-09:22 0.00 0.00 0.00 -4909.14 0.00 0.00 0.00 724.15 217.24 2131.53 0.00 39.85 1796.37 0.00 -0.00 0.00 0.00 0.00
PERIMETER_ZN_3 29-JUL-17:22 0.00 0.00 0.00 -5154.78 0.00 0.00 0.00 0.00 366.22 604.08 0.00 184.85 3999.63 0.00 -0.00 0.00 0.00 0.00
PERIMETER_ZN_4 08-APR-17:12 0.00 0.00 0.00 -5584.40 0.00 0.00 0.00 724.15 217.24 1859.25 0.00 0.00 2825.14 0.00 -0.00 0.00 -41.39 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 03-JUN-17:33 0.00 0.00 0.00 -23034.72 0.00 0.00 0.00 1220.72 1650.02 1799.41 0.00 519.04 20789.66 0.00 0.00 0.00 -2944.13 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 03-APR-05:10 0.00 0.00 805.74 0.00 0.00 0.00 51.33 0.00 644.13 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -47.25 -1453.94
PERIMETER_ZN_1 20-APR-05:10 0.00 0.00 912.06 0.00 0.00 0.00 37.12 1220.72 488.29 0.00 0.00 0.00 0.00 0.00 -448.35 0.00 -22.50 -2187.33
PERIMETER_ZN_2 17-OCT-05:06 0.00 0.00 889.97 0.00 0.00 0.00 21.10 0.00 289.66 0.00 0.00 0.00 0.00 0.00 -180.56 0.00 -0.11 -1020.06
PERIMETER_ZN_3 05-FEB-06:05 0.00 0.00 1938.72 0.00 0.00 0.00 52.27 0.00 488.29 0.00 0.00 0.00 0.00 0.00 -700.16 0.00 -79.28 -1699.84
PERIMETER_ZN_4 09-MAY-05:16 0.00 0.00 1036.50 0.00 0.00 0.00 20.29 0.00 289.66 0.00 0.00 0.00 0.00 0.00 -150.21 0.00 -0.60 -1195.64
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 03-APR-05:10 0.00 0.00 3242.42 0.00 0.00 0.00 173.13 724.15 2200.02 0.00 0.00 609.08 0.00 0.00 -1556.53 0.00 -138.41 -5253.86



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-07-07 15:38:44

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA
PSZ-AC:1 0.291 8.05 8.05 1.00 0.0805 0.291 0.277 1.000 0.0805 0.28
PSZ-AC:2 0.271 6.11 6.11 1.00 0.0611 0.271 0.225 1.000 0.0611 0.23
PSZ-AC:3 0.301 3.62 3.62 1.00 0.0362 0.301 0.120 1.000 0.0362 0.12
PSZ-AC:4 0.296 6.11 6.11 1.00 0.0611 0.296 0.207 1.000 0.0611 0.21
PSZ-AC:5 0.328 3.62 3.62 1.00 0.0362 0.328 0.110 1.000 0.0362 0.11


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA
PSZ-AC:1 0.081 8.05 8.05 1.00 0.0805 0.081 1.000 1.000 0.0805 1.00
PSZ-AC:2 0.134 6.11 6.11 1.00 0.0611 0.134 1.000 1.000 0.0611 0.46
PSZ-AC:3 0.087 3.62 3.62 1.00 0.0362 0.087 1.000 1.000 0.0362 0.42
PSZ-AC:4 0.128 6.11 6.11 1.00 0.0611 0.128 1.000 1.000 0.0611 0.48
PSZ-AC:5 0.087 3.62 3.62 1.00 0.0362 0.087 1.000 1.000 0.0362 0.42


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORE_ZN PSZ-AC:1 0.010000 8.05 0.000000 149.66 0.0805 1.000 0.0805 1.000 0.0805
PERIMETER_ZN_1 PSZ-AC:2 0.010000 6.11 0.000000 113.45 0.0611 1.000 0.0611 1.000 0.0611
PERIMETER_ZN_2 PSZ-AC:3 0.010000 3.62 0.000000 67.30 0.0362 1.000 0.0362 1.000 0.0362
PERIMETER_ZN_3 PSZ-AC:4 0.010000 6.11 0.000000 113.45 0.0611 1.000 0.0611 1.000 0.0611
PERIMETER_ZN_4 PSZ-AC:5 0.010000 3.62 0.000000 67.30 0.0362 1.000 0.0362 1.000 0.0362


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PSZ-AC:1 0.010000 8.05 0.000000 149.66 0.0805 0.0805 0.0805
PSZ-AC:2 0.010000 6.11 0.000000 113.45 0.0611 0.0611 0.0611
PSZ-AC:3 0.010000 3.62 0.000000 67.30 0.0362 0.0362 0.0362
PSZ-AC:4 0.010000 6.11 0.000000 113.45 0.0611 0.0611 0.0611
PSZ-AC:5 0.010000 3.62 0.000000 67.30 0.0362 0.0362 0.0362


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1   0.291 0.2911 0.1140 0.0805 0.000 1.000 0.000 0.000 0.000 0.000 1.000
PERIMETER_ZN_1 PSZ-AC:2   0.271 0.2712 0.0864 0.0611 0.000 1.000 0.000 0.000 0.000 0.000 1.000
PERIMETER_ZN_2 PSZ-AC:3   0.301 0.3010 0.0602 0.0362 0.000 1.000 0.000 0.000 0.000 0.000 1.000
PERIMETER_ZN_3 PSZ-AC:4   0.296 0.2955 0.0864 0.0611 0.000 1.000 0.000 0.000 0.000 0.000 1.000
PERIMETER_ZN_4 PSZ-AC:5   0.328 0.3279 0.0656 0.0362 0.000 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.29 0.291 0.29 0.1140 0.0805 1.000
PSZ-AC:2 0.27 0.271 0.27 0.0864 0.0611 1.000
PSZ-AC:3 0.30 0.301 0.30 0.0602 0.0362 1.000
PSZ-AC:4 0.30 0.296 0.30 0.0864 0.0611 1.000
PSZ-AC:5 0.33 0.328 0.33 0.0656 0.0362 1.000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1   0.081 0.081 0.081 0.0805 1.000 1.000 0.000 0.000 0.000 0.000 1.000
PERIMETER_ZN_1 PSZ-AC:2   0.134 0.134 0.134 0.0611 0.456 1.000 0.000 0.000 0.000 0.000 1.000
PERIMETER_ZN_2 PSZ-AC:3   0.087 0.087 0.087 0.0362 0.415 1.000 0.000 0.000 0.000 0.000 1.000
PERIMETER_ZN_3 PSZ-AC:4   0.128 0.128 0.128 0.0611 0.477 1.000 0.000 0.000 0.000 0.000 1.000
PERIMETER_ZN_4 PSZ-AC:5   0.087 0.087 0.087 0.0362 0.416 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.08 0.081 0.08 0.08 0.0805 1.000
PSZ-AC:2 0.13 0.134 0.13 0.13 0.0611 1.000
PSZ-AC:3 0.09 0.087 0.09 0.09 0.0362 1.000
PSZ-AC:4 0.13 0.128 0.13 0.13 0.0611 1.000
PSZ-AC:5 0.09 0.087 0.09 0.09 0.0362 1.000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-07-07 15:38:44

Sec1.1A-General Information

Data
Weather File Miami Intl Ap FL USA TMY3 WMO#=722020
Total gross floor area [m2] 511.16
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORE_ZN 149.66 149.66 0.00 97.62
PERIMETER_ZN_1 113.45 113.45 0.00 97.62
PERIMETER_ZN_2 67.30 67.30 0.00 97.62
PERIMETER_ZN_3 113.45 113.45 0.00 97.62
PERIMETER_ZN_4 67.30 67.30 0.00 97.62
ATTIC 567.98 0.00 567.98 0.00
Totals 511.16 511.16 567.98  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 114.50
Number of hours not met 114.50


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
Electricity FPL_GS-1_NONDEMAND 0.102 kWh kW
Natural Gas FL_EIAMONTHLYRATEGAS 12.101 MCF MCF/Hr
Other        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [GJ] Electric Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Additional Energy Use [GJ] Additional Demand [W]
Interior Lighting 56.31 5500.05 0.00 0.00 0.00 0.00
Exterior Lighting 36.24 0.00 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 0.27 5917.20 0.00 0.00
Space Cooling 69.71 7346.50 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 34.02 1724.56 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 10.19 20.00 0.00 0.00
Receptacle Equipment 87.61 4950.05 0.00 0.00 0.00 0.00
Interior Lighting-Process 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 283.89   10.46   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 87.61 283.89
Natural Gas 0.00 10.46
Total 87.61 294.35
Additional 0.00 0.00


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 2491.24 8072.27
Natural Gas 0.00 119.95
Other   0.00
Total 2491.24 8192.22
Additional 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting 110.16
Space Heating 0.00
Space Cooling 136.38
Fans-Interior 66.55
Service Water Heating 0.00
Receptacle Equipment 171.40
Miscellaneous 70.89
Subtotal 555.39


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.52
Service Water Heating 19.94
Miscellaneous -0.00
Subtotal 20.46


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 19.13
Space Heating 0.09
Space Cooling 23.68
Fans-Interior 11.56
Service Water Heating 3.46
Receptacle Equipment 29.77
Miscellaneous 12.31



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-07-07 15:38:44

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [m3/s]
CORE_ZN DIRECT AIR 0.291130
PERIMETER_ZN_1 DIRECT AIR 0.271196
PERIMETER_ZN_2 DIRECT AIR 0.301023
PERIMETER_ZN_3 DIRECT AIR 0.295541
PERIMETER_ZN_4 DIRECT AIR 0.327920
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
PSZ-AC:1 0.291130
PSZ-AC:2 0.271196
PSZ-AC:3 0.301023
PSZ-AC:4 0.295541
PSZ-AC:5 0.327920
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
PSZ-AC:1_OA_CONTROLLER 0.291130 0.080548
PSZ-AC:2_OA_CONTROLLER 0.271196 0.061060
PSZ-AC:3_OA_CONTROLLER 0.301023 0.036222
PSZ-AC:4_OA_CONTROLLER 0.295541 0.061060
PSZ-AC:5_OA_CONTROLLER 0.327920 0.036222
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Total Cooling Capacity [W] Design Size Gross Rated Sensible Heat Ratio
PSZ-AC:1_COOLC DXCOIL 0.291130 7229.45 0.676083
PSZ-AC:2_COOLC DXCOIL 0.271196 6734.44 0.676083
PSZ-AC:3_COOLC DXCOIL 0.301023 6100.96 0.731285
PSZ-AC:4_COOLC DXCOIL 0.295541 6774.96 0.696487
PSZ-AC:5_COOLC DXCOIL 0.327920 6658.65 0.730718
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
PSZ-AC:1_HEATC 7950.90
PSZ-AC:2_HEATC 7186.98
PSZ-AC:3_HEATC 7481.71
PSZ-AC:4_HEATC 7746.03
PSZ-AC:5_HEATC 8099.35
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
PSZ-AC:1_FAN 0.291130
PSZ-AC:2_FAN 0.271196
PSZ-AC:3_FAN 0.301023
PSZ-AC:4_FAN 0.295541
PSZ-AC:5_FAN 0.327920
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYS1 0.000003 0.000378
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000003 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000003
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-07-07 15:38:44

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_WEST |
PERIMETER_ZN_2_WALL_EAST ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH | ATTIC_SOFFIT_SOUTH |
PERIMETER_ZN_3_WALL_NORTH ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH | ATTIC_SOFFIT_WEST |
PERIMETER_ZN_4_WALL_WEST ATTIC_SOFFIT_NORTH | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_WEST |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR |
PERIMETER_ZN_2_WALL_EAST PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 |
PERIMETER_ZN_3_WALL_NORTH PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 |
PERIMETER_ZN_4_WALL_WEST PERIMETER_ZN_4_WALL_WEST_WINDOW_1 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-07-07 15:38:44

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-07-07 15:38:44

Version

Version ID
1 8.7


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 2 25 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 22.51 22.64 22.78 22.96 23.05 23.08 23.12 23.11 23.13 23.14 23.08 22.91


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 22.26 20.91 20.55 20.86 22.68 24.72 26.64 28.02 28.43 27.78 26.21 24.23


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Miami Intl Ap FL USA TMY3 WMO#=722020 25.82 -80.30 -5.00 11.00 101193 1.2027


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 Ref Bldg Small Office New2004_v1.3_5.0 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 Yes YES


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance

Adjust Zone Mixing

Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}
Infiltration Zones {MixingSourceZonesOnly
AllZones}
1 No N/A N/A N/A


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 6 69 21


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 ATTIC 0.0 0.00 0.00 0.00 13.85 9.23 3.70 1 1 1 -0.60 28.29 -0.60 19.06 3.05 6.33 1.64 720.19 TARP DOE-2 567.98 0.00 0.00 0.00 13 0 0 No
2 CORE_ZN 0.0 0.00 0.00 0.00 13.85 9.23 1.53 1 1 1 5.00 22.69 5.00 13.46 0.00 3.05 3.05 456.46 TARP DOE-2 149.66 0.00 0.00 0.00 6 0 0 Yes
3 PERIMETER_ZN_1 0.0 0.00 0.00 0.00 13.85 2.21 1.53 1 1 1 0.00 27.69 0.00 5.00 0.00 3.05 3.05 346.02 TARP DOE-2 113.45 84.45 63.82 20.64 6 7 0 Yes
4 PERIMETER_ZN_2 0.0 0.00 0.00 0.00 25.64 9.23 1.53 1 1 1 22.69 27.69 0.00 18.46 0.00 3.05 3.05 205.27 TARP DOE-2 67.30 56.30 45.15 11.16 6 4 0 Yes
5 PERIMETER_ZN_3 0.0 0.00 0.00 0.00 13.85 16.25 1.53 1 1 1 0.00 27.69 13.46 18.46 0.00 3.05 3.05 346.02 TARP DOE-2 113.45 84.45 67.72 16.73 6 6 0 Yes
6 PERIMETER_ZN_4 0.0 0.00 0.00 0.00 2.05 9.23 1.53 1 1 1 0.00 5.00 0.00 18.46 0.00 3.05 3.05 205.27 TARP DOE-2 67.30 56.30 45.15 11.16 6 4 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 ATTIC 567.98 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
2 CORE_ZN 149.66 8.1 18.580 5.382E-002 10.760 10.760 0.000 0.000 0.000 0.000 21.520 No
3 PERIMETER_ZN_1 113.45 6.1 18.580 5.382E-002 10.760 10.760 0.000 0.000 0.000 0.000 21.520 No
4 PERIMETER_ZN_2 67.30 3.6 18.580 5.382E-002 10.760 10.760 0.000 0.000 0.000 0.000 21.520 No
5 PERIMETER_ZN_3 113.45 6.1 18.580 5.382E-002 10.760 10.760 0.000 0.000 0.000 0.000 21.520 No
6 PERIMETER_ZN_4 67.30 3.6 18.580 5.382E-002 10.760 10.760 0.000 0.000 0.000 0.000 21.520 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation
1 CORE_ZN PEOPLE BLDG_OCC_SCH CORE_ZN 149.66 8.1 8.1 5.382E-002 18.580 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
2 PERIMETER_ZN_1 PEOPLE BLDG_OCC_SCH PERIMETER_ZN_1 113.45 6.1 6.1 5.382E-002 18.580 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
3 PERIMETER_ZN_2 PEOPLE BLDG_OCC_SCH PERIMETER_ZN_2 67.30 3.6 3.6 5.382E-002 18.580 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
4 PERIMETER_ZN_3 PEOPLE BLDG_OCC_SCH PERIMETER_ZN_3 113.45 6.1 6.1 5.382E-002 18.580 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No
5 PERIMETER_ZN_4 PEOPLE BLDG_OCC_SCH PERIMETER_ZN_4 67.30 3.6 3.6 5.382E-002 18.580 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORE_ZN_LIGHTS ZONE_LIGHT_SCH_CORE_ZN CORE_ZN 149.66 8.1 1610.314 10.760 199.921 0.000 0.700 0.200 0.100 1.000 General 0.000 0.000
2 PERIMETER_ZN_1_LIGHTS ZONE_LIGHT_SCH_PERIMETER_ZN_1 PERIMETER_ZN_1 113.45 6.1 1220.722 10.760 199.921 0.000 0.700 0.200 0.100 1.000 General 0.000 0.000
3 PERIMETER_ZN_2_LIGHTS ZONE_LIGHT_SCH_PERIMETER_ZN_2 PERIMETER_ZN_2 67.30 3.6 724.148 10.760 199.921 0.000 0.700 0.200 0.100 1.000 General 0.000 0.000
4 PERIMETER_ZN_3_LIGHTS ZONE_LIGHT_SCH_PERIMETER_ZN_3 PERIMETER_ZN_3 113.45 6.1 1220.722 10.760 199.921 0.000 0.700 0.200 0.100 1.000 General 0.000 0.000
5 PERIMETER_ZN_4_LIGHTS ZONE_LIGHT_SCH_PERIMETER_ZN_4 PERIMETER_ZN_4 67.30 3.6 724.148 10.760 199.921 0.000 0.700 0.200 0.100 1.000 General 0.000 0.000


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 CORE_ZN_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_ZN 149.66 8.1 1610.314 10.760 199.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1610.314
2 PERIMETER_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_1 113.45 6.1 1220.722 10.760 199.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1220.722
3 PERIMETER_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_2 67.30 3.6 724.148 10.760 199.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 724.148
4 PERIMETER_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_3 113.45 6.1 1220.722 10.760 199.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 1220.722
5 PERIMETER_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_4 67.30 3.6 724.148 10.760 199.921 0.000 0.500 0.000 0.500 MiscPlug 0.000 724.148


Shadowing/Sun Position Calculations Annual Simulations

Calculation Method Value {days} Allowable Number Figures in Shadow Overlap {} Polygon Clipping Algorithm Sky Diffuse Modeling Algorithm
1 AverageOverDaysInFrequency 7 15000 SutherlandHodgman SimpleSkyDiffuseModeling


Zone/Window Adjacency Daylighting Counts

Zone Name Number of Exterior Windows Number of Exterior Windows in Adjacent Zones
1 CORE_ZN 0 0
2 PERIMETER_ZN_1 7 0
3 PERIMETER_ZN_2 4 0
4 PERIMETER_ZN_3 6 0
5 PERIMETER_ZN_4 4 0


Zone/Window Adjacency Daylighting Matrix

Zone Name Number of Adjacent Zones with Windows Adjacent Zone Names - 1st 100 (max)
1 CORE_ZN 0  
2 PERIMETER_ZN_1 0  
3 PERIMETER_ZN_2 0  
4 PERIMETER_ZN_3 0  
5 PERIMETER_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.1514 845000.0 4.580 0.5740


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s/m2} Volume Flow Rate/Exterior Surface Area {m3/s/m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 CORE_ZN_INFILTRATION INFIL_QUARTER_ON_SCH CORE_ZN 149.66 8.1 4.565E-002 3.050E-004 N/A 0.360 1.000 0.000 0.000 0.000
2 PERIMETER_ZN_1_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_1 113.45 6.1 2.551E-002 2.248E-004 3.020E-004 0.265 1.000 0.000 0.000 0.000
3 PERIMETER_ZN_2_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_2 67.30 3.6 1.700E-002 2.527E-004 3.020E-004 0.298 1.000 0.000 0.000 0.000
4 PERIMETER_ZN_3_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_3 113.45 6.1 2.551E-002 2.248E-004 3.020E-004 0.265 1.000 0.000 0.000 0.000
5 PERIMETER_ZN_4_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_4 67.30 3.6 1.700E-002 2.527E-004 3.020E-004 0.298 1.000 0.000 0.000 0.000
6 ATTIC_INFILTRATION ALWAYS_ON ATTIC 567.98 0.0 0.200 3.522E-004 3.052E-004 1.000 1.000 0.000 0.000 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 ATTIC Mixing/Well-Stirred
2 CORE_ZN Mixing/Well-Stirred
3 PERIMETER_ZN_1 Mixing/Well-Stirred
4 PERIMETER_ZN_2 Mixing/Well-Stirred
5 PERIMETER_ZN_3 Mixing/Well-Stirred
6 PERIMETER_ZN_4 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORE_ZN Cooling 3150.60346 3780.72415 0.24261 0.29113 MIAMI ANN CLG .4% CONDNS WB=>MDB 7/21 07:00:00 24.40300 1.93614E-002 149.65740 8.05476 8.05476E-002 0.00000
2 CORE_ZN Heating 1040.06724 1248.08069 4.46321E-002 8.05476E-002 MIAMI ANN HTG 99.6% CONDNS DB 1/21 06:00:00 8.00000 6.65766E-003 149.65740 8.05476 8.05476E-002 0.00000
3 PERIMETER_ZN_1 Cooling 2774.01303 3328.81563 0.22600 0.27120 MIAMI ANN CLG .4% CONDNS WB=>MDB 7/21 16:50:00 29.65133 2.06742E-002 113.45000 6.10603 6.10603E-002 0.00000
4 PERIMETER_ZN_1 Heating 2598.08078 3117.69694 0.11149 0.13379 MIAMI ANN HTG 99.6% CONDNS DB 1/21 06:00:00 8.00000 6.65766E-003 113.45000 6.10603 6.10603E-002 0.00000
5 PERIMETER_ZN_2 Cooling 3079.19823 3695.03788 0.25085 0.30102 MIAMI ANN CLG .4% CONDNS WB=>MDB 7/21 09:20:00 27.19467 2.06742E-002 67.30000 3.62217 3.62217E-002 0.00000
6 PERIMETER_ZN_2 Heating 1693.84601 2032.61521 7.26872E-002 8.72247E-002 MIAMI ANN HTG 99.6% CONDNS DB 1/21 06:00:00 8.00000 6.65766E-003 67.30000 3.62217 3.62217E-002 0.00000
7 PERIMETER_ZN_3 Cooling 3022.59240 3627.11088 0.24628 0.29554 MIAMI ANN CLG .4% CONDNS WB=>MDB 7/21 07:20:00 24.78267 1.98201E-002 113.45000 6.10603 6.10603E-002 0.00000
8 PERIMETER_ZN_3 Heating 2486.77278 2984.12733 0.10671 0.12806 MIAMI ANN HTG 99.6% CONDNS DB 1/21 06:00:00 8.00000 6.65766E-003 113.45000 6.10603 6.10603E-002 0.00000
9 PERIMETER_ZN_4 Cooling 3354.28544 4025.14253 0.27327 0.32792 MIAMI ANN CLG .4% CONDNS WB=>MDB 7/21 17:40:00 29.11533 2.06742E-002 67.30000 3.62217 3.62217E-002 0.00000
10 PERIMETER_ZN_4 Heating 1688.89755 2026.67707 7.24749E-002 8.69699E-002 MIAMI ANN HTG 99.6% CONDNS DB 1/21 06:00:00 8.00000 6.65766E-003 67.30000 3.62217 3.62217E-002 0.00000


System Sizing Information

System Name Field Description Value
1 PSZ-AC:1 Calculated Cooling Design Air Flow Rate [m3/s] 0.29113
2 PSZ-AC:1 User Cooling Design Air Flow Rate [m3/s] 0.29113
3 PSZ-AC:1 Calculated Heating Design Air Flow Rate [m3/s] 8.05476E-002
4 PSZ-AC:1 User Heating Design Air Flow Rate [m3/s] 8.05476E-002
5 PSZ-AC:2 Calculated Cooling Design Air Flow Rate [m3/s] 0.27120
6 PSZ-AC:2 User Cooling Design Air Flow Rate [m3/s] 0.27120
7 PSZ-AC:2 Calculated Heating Design Air Flow Rate [m3/s] 0.13379
8 PSZ-AC:2 User Heating Design Air Flow Rate [m3/s] 0.13379
9 PSZ-AC:3 Calculated Cooling Design Air Flow Rate [m3/s] 0.30102
10 PSZ-AC:3 User Cooling Design Air Flow Rate [m3/s] 0.30102
11 PSZ-AC:3 Calculated Heating Design Air Flow Rate [m3/s] 8.72247E-002
12 PSZ-AC:3 User Heating Design Air Flow Rate [m3/s] 8.72247E-002
13 PSZ-AC:4 Calculated Cooling Design Air Flow Rate [m3/s] 0.29554
14 PSZ-AC:4 User Cooling Design Air Flow Rate [m3/s] 0.29554
15 PSZ-AC:4 Calculated Heating Design Air Flow Rate [m3/s] 0.12806
16 PSZ-AC:4 User Heating Design Air Flow Rate [m3/s] 0.12806
17 PSZ-AC:5 Calculated Cooling Design Air Flow Rate [m3/s] 0.32792
18 PSZ-AC:5 User Cooling Design Air Flow Rate [m3/s] 0.32792
19 PSZ-AC:5 Calculated Heating Design Air Flow Rate [m3/s] 8.69699E-002
20 PSZ-AC:5 User Heating Design Air Flow Rate [m3/s] 8.69699E-002


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:Uncontrolled CORE_ZN DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.29113
2 AirTerminal:SingleDuct:Uncontrolled PERIMETER_ZN_1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.27120
3 AirTerminal:SingleDuct:Uncontrolled PERIMETER_ZN_2 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.30102
4 AirTerminal:SingleDuct:Uncontrolled PERIMETER_ZN_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.29554
5 AirTerminal:SingleDuct:Uncontrolled PERIMETER_ZN_4 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.32792
6 AirLoopHVAC PSZ-AC:1 Design Supply Air Flow Rate [m3/s] 0.29113
7 AirLoopHVAC PSZ-AC:2 Design Supply Air Flow Rate [m3/s] 0.27120
8 AirLoopHVAC PSZ-AC:3 Design Supply Air Flow Rate [m3/s] 0.30102
9 AirLoopHVAC PSZ-AC:4 Design Supply Air Flow Rate [m3/s] 0.29554
10 AirLoopHVAC PSZ-AC:5 Design Supply Air Flow Rate [m3/s] 0.32792
11 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.29113
12 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 8.05476E-002
13 Coil:Cooling:DX:SingleSpeed PSZ-AC:1_COOLC DXCOIL Design Size Rated Air Flow Rate [m3/s] 0.29113
14 Coil:Cooling:DX:SingleSpeed PSZ-AC:1_COOLC DXCOIL Design Size Gross Rated Total Cooling Capacity [W] 7229.45189
15 Coil:Cooling:DX:SingleSpeed PSZ-AC:1_COOLC DXCOIL Design Size Gross Rated Sensible Heat Ratio 0.67608
16 Coil:Heating:Fuel PSZ-AC:1_HEATC Design Size Nominal Capacity [W] 7950.89900
17 Fan:ConstantVolume PSZ-AC:1_FAN Design Size Maximum Flow Rate [m3/s] 0.29113
18 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.27120
19 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 6.10603E-002
20 Coil:Cooling:DX:SingleSpeed PSZ-AC:2_COOLC DXCOIL Design Size Rated Air Flow Rate [m3/s] 0.27120
21 Coil:Cooling:DX:SingleSpeed PSZ-AC:2_COOLC DXCOIL Design Size Gross Rated Total Cooling Capacity [W] 6734.43606
22 Coil:Cooling:DX:SingleSpeed PSZ-AC:2_COOLC DXCOIL Design Size Gross Rated Sensible Heat Ratio 0.67608
23 Coil:Heating:Fuel PSZ-AC:2_HEATC Design Size Nominal Capacity [W] 7186.97629
24 Fan:ConstantVolume PSZ-AC:2_FAN Design Size Maximum Flow Rate [m3/s] 0.27120
25 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.30102
26 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 3.62217E-002
27 Coil:Cooling:DX:SingleSpeed PSZ-AC:3_COOLC DXCOIL Design Size Rated Air Flow Rate [m3/s] 0.30102
28 Coil:Cooling:DX:SingleSpeed PSZ-AC:3_COOLC DXCOIL Design Size Gross Rated Total Cooling Capacity [W] 6100.95546
29 Coil:Cooling:DX:SingleSpeed PSZ-AC:3_COOLC DXCOIL Design Size Gross Rated Sensible Heat Ratio 0.73129
30 Coil:Heating:Fuel PSZ-AC:3_HEATC Design Size Nominal Capacity [W] 7481.70847
31 Fan:ConstantVolume PSZ-AC:3_FAN Design Size Maximum Flow Rate [m3/s] 0.30102
32 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.29554
33 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 6.10603E-002
34 Coil:Cooling:DX:SingleSpeed PSZ-AC:4_COOLC DXCOIL Design Size Rated Air Flow Rate [m3/s] 0.29554
35 Coil:Cooling:DX:SingleSpeed PSZ-AC:4_COOLC DXCOIL Design Size Gross Rated Total Cooling Capacity [W] 6774.95744
36 Coil:Cooling:DX:SingleSpeed PSZ-AC:4_COOLC DXCOIL Design Size Gross Rated Sensible Heat Ratio 0.69649
37 Coil:Heating:Fuel PSZ-AC:4_HEATC Design Size Nominal Capacity [W] 7746.02968
38 Fan:ConstantVolume PSZ-AC:4_FAN Design Size Maximum Flow Rate [m3/s] 0.29554
39 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.32792
40 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 3.62217E-002
41 Coil:Cooling:DX:SingleSpeed PSZ-AC:5_COOLC DXCOIL Design Size Rated Air Flow Rate [m3/s] 0.32792
42 Coil:Cooling:DX:SingleSpeed PSZ-AC:5_COOLC DXCOIL Design Size Gross Rated Total Cooling Capacity [W] 6658.65456
43 Coil:Cooling:DX:SingleSpeed PSZ-AC:5_COOLC DXCOIL Design Size Gross Rated Sensible Heat Ratio 0.73072
44 Coil:Heating:Fuel PSZ-AC:5_HEATC Design Size Nominal Capacity [W] 8099.35060
45 Fan:ConstantVolume PSZ-AC:5_FAN Design Size Maximum Flow Rate [m3/s] 0.32792
46 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.15000E-006
47 PlantLoop SWHSYS1 Plant Loop Volume [m3] 3.78000E-004
48 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.15000E-006
49 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 4.03846E-009
50 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 3.15000E-006


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed PSZ-AC:1_COOLC DXCOIL 7003.6 3.19 10.88 12.53 12.16
2 Coil:Cooling:DX:SingleSpeed PSZ-AC:2_COOLC DXCOIL 6524.0 3.19 10.88 12.53 12.16
3 Coil:Cooling:DX:SingleSpeed PSZ-AC:3_COOLC DXCOIL 5867.6 3.09 10.56 12.12 11.55
4 Coil:Cooling:DX:SingleSpeed PSZ-AC:4_COOLC DXCOIL 6545.7 3.15 10.76 12.38 11.93
5 Coil:Cooling:DX:SingleSpeed PSZ-AC:5_COOLC DXCOIL 6404.4 3.09 10.56 12.13 11.56


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values
1 Miami Intl Ap FL USA TMY3 WMO#=722020 WeatherFileRunPeriod 01/01 12/31 Monday 365 Use RunPeriod Specified Day No No Yes Yes Yes


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1
2 VETERANS DAY Holiday InputFile 11/12 1
3 CHRISTMAS Holiday InputFile 12/25 1
4 INDEPENDENCE DAY Holiday InputFile 07/04 1
5 MLK DAY Holiday InputFile 01/15 1
6 PRESIDENTS DAY Holiday InputFile 02/19 1
7 MEMORIAL DAY Holiday InputFile 05/28 1
8 LABOR DAY Holiday InputFile 09/03 1
9 COLUMBUS DAY Holiday InputFile 10/08 1
10 THANKSGIVING Holiday InputFile 11/22 1


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/11 11/04


Environment:WarmupDays

NumberofWarmupDays
1 7


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 ATTIC RunPeriod: Miami Intl Ap FL USA TMY3 WMO#=722020 0.3886093456 0.3683788400 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 CORE_ZN RunPeriod: Miami Intl Ap FL USA TMY3 WMO#=722020 1.3815785472E-002 1.3856451999E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 PERIMETER_ZN_1 RunPeriod: Miami Intl Ap FL USA TMY3 WMO#=722020 0.2010932978 0.2429997562 Pass Pass 0.4763263976 1.0546169523 Pass Pass
4 PERIMETER_ZN_2 RunPeriod: Miami Intl Ap FL USA TMY3 WMO#=722020 4.9247427442E-002 6.4322338222E-002 Pass Pass 3.7127633798E-002 0.2375271118 Pass Pass
5 PERIMETER_ZN_3 RunPeriod: Miami Intl Ap FL USA TMY3 WMO#=722020 2.0607976986E-002 1.6727601136E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
6 PERIMETER_ZN_4 RunPeriod: Miami Intl Ap FL USA TMY3 WMO#=722020 2.9843802360E-002 2.2338887916E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Economics Results Summary Report

For: Entire Facility

Timestamp: 2024-07-07 15:38:44

Annual Cost

Electric Gas Other Total
Cost [$] 8072.27 119.95 0.00 8192.22
Cost per Total Building Area [$/m2] 15.79 0.23 0.00 16.03
Cost per Net Conditioned Building Area [$/m2] 15.79 0.23 0.00 16.03


Tariff Summary

Selected Qualified Meter Buy or Sell Group Annual Cost ($)
FPL_GSLD-1_GENERALSERVICELARGEDEMAND No No ELECTRICITY:FACILITY Buy COMM ELECT 6759.30
FPL_GSD-1_GENERALSERVICEDEMAND No No ELECTRICITY:FACILITY Buy COMM ELECT 5868.39
FPL_GS-1_NONDEMAND Yes Yes ELECTRICITY:FACILITY Buy COMM ELECT 8072.27
FL_EIAMONTHLYRATEGAS Yes Yes GAS:FACILITY Buy COMM GAS 119.95



Table of Contents

Report: Tariff Report

For: FPL_GSLD-1_GENERALSERVICELARGEDEMAND

Timestamp: 2024-07-07 15:38:44

General

Parameter
Meter ELECTRICITY:FACILITY
Selected No
Group COMM ELECT
Qualified No
Disqualifier MINDEMAND500KW
Computation automatic
Units kWh


Categories

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
EnergyCharges ($) 296.92 268.16 319.18 332.01 374.19 359.37 386.68 396.33 369.64 369.71 335.20 309.36 4116.76 396.33
DemandCharges ($) 124.61 127.70 132.71 137.16 145.49 149.50 150.23 153.68 148.16 144.45 135.55 135.15 1684.41 153.68
ServiceCharges ($) 38.12 38.12 38.12 38.12 38.12 38.12 38.12 38.12 38.12 38.12 38.12 38.12 457.44 38.12
Basis ($) 459.66 433.98 490.01 507.29 557.80 547.00 575.03 588.13 555.92 552.28 508.87 482.62 6258.61 588.13
Adjustment ($) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Surcharge ($) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Subtotal ($) 459.66 433.98 490.01 507.29 557.80 547.00 575.03 588.13 555.92 552.28 508.87 482.62 6258.61 588.13
Taxes ($) 36.77 34.72 39.20 40.58 44.62 43.76 46.00 47.05 44.47 44.18 40.71 38.61 500.69 47.05
Total ($) 496.43 468.70 529.21 547.88 602.42 590.76 621.04 635.18 600.39 596.47 549.58 521.23 6759.30 635.18


Charges

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max Category
NON-FUELENERGYCHARGE ($) 61.43 55.48 66.04 68.69 77.42 74.35 80.00 82.00 76.48 76.49 69.35 64.01 851.74 82.00 EnergyCharges
FUELENERGYCHARGE ($) 227.53 205.49 244.58 254.42 286.73 275.38 296.31 303.70 283.25 283.30 256.86 237.06 3154.60 303.70 EnergyCharges
CONSERVATIONENERGYCHARGE ($) 6.83 6.16 7.34 7.63 8.60 8.26 8.89 9.11 8.50 8.50 7.71 7.11 94.64 9.11 EnergyCharges
ENVIRONMENTALENERGYCHARGE ($) 1.14 1.03 1.22 1.27 1.43 1.38 1.48 1.52 1.42 1.42 1.28 1.19 15.77 1.52 EnergyCharges
TAXOFEIGHTPERCENT ($) 36.77 34.72 39.20 40.58 44.62 43.76 46.00 47.05 44.47 44.18 40.71 38.61 500.69 47.05 Taxes
ANNUALDEMANDBASECHARGE ($) 86.81 88.96 92.45 95.55 101.35 104.15 104.66 107.06 103.22 100.63 94.43 94.15 1173.43 107.06 DemandCharges
ANNUALDEMANDCAPACITYCHARGE ($) 37.80 38.74 40.26 41.61 44.14 45.35 45.57 46.62 44.95 43.82 41.12 41.00 510.98 46.62 DemandCharges


Corresponding Sources for Charges

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
Subtotal 459.66 433.98 490.01 507.29 557.80 547.00 575.03 588.13 555.92 552.28 508.87 482.62 6258.61 588.13
TotalEnergy 5688.15 5137.15 6114.58 6360.41 7168.36 6884.56 7407.68 7592.54 7081.16 7082.61 6421.45 5926.40 78865.05 7592.54
TotalDemand 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43


Ratchets

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max


Qualifies

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
MAXDEMAND3000KW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
MINDEMAND500KW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Native Variables

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
TotalEnergy 5688.15 5137.15 6114.58 6360.41 7168.36 6884.56 7407.68 7592.54 7081.16 7082.61 6421.45 5926.40 78865.05 7592.54
TotalDemand 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43
PeakEnergy 5688.15 5137.15 6114.58 6360.41 7168.36 6884.56 7407.68 7592.54 7081.16 7082.61 6421.45 5926.40 78865.05 7592.54
PeakDemand 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43
ShoulderEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ShoulderDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
OffPeakEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
OffPeakDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MidPeakEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MidPeakDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakExceedsOffPeak 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43
OffPeakExceedsPeak 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakExceedsMidPeak 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43
MidPeakExceedsPeak 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakExceedsShoulder 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43
ShoulderExceedsPeak 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsWinter 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
IsNotWinter 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsSpring 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsNotSpring 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
IsSummer 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsNotSummer 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
IsAutumn 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsNotAutumn 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
PeakAndShoulderEnergy 5688.15 5137.15 6114.58 6360.41 7168.36 6884.56 7407.68 7592.54 7081.16 7082.61 6421.45 5926.40 78865.05 7592.54
PeakAndShoulderDemand 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43
PeakAndMidPeakEnergy 5688.15 5137.15 6114.58 6360.41 7168.36 6884.56 7407.68 7592.54 7081.16 7082.61 6421.45 5926.40 78865.05 7592.54
PeakAndMidPeakDemand 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43
ShoulderAndOffPeakEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ShoulderAndOffPeakDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakAndOffPeakEnergy 5688.15 5137.15 6114.58 6360.41 7168.36 6884.56 7407.68 7592.54 7081.16 7082.61 6421.45 5926.40 78865.05 7592.54
PeakAndOffPeakDemand 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43
RealTimePriceCosts 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AboveCustomerBaseCosts 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BelowCustomerBaseCosts 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AboveCustomerBaseEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BelowCustomerBaseEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Other Variables

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
NotIncluded 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Computation - Automatic

MAXDEMAND3000KW FROM TotalDemand
MINDEMAND500KW FROM TotalDemand
NON-FUELENERGYCHARGE FROM TotalEnergy
FUELENERGYCHARGE FROM TotalEnergy
CONSERVATIONENERGYCHARGE FROM TotalEnergy
ENVIRONMENTALENERGYCHARGE FROM TotalEnergy
ANNUALDEMANDBASECHARGE FROM TotalDemand
ANNUALDEMANDCAPACITYCHARGE FROM TotalDemand
EnergyCharges SUM NON-FUELENERGYCHARGE FUELENERGYCHARGE CONSERVATIONENERGYCHARGE ENVIRONMENTALENERGYCHARGE
DemandCharges SUM ANNUALDEMANDBASECHARGE ANNUALDEMANDCAPACITYCHARGE
Basis SUM EnergyCharges DemandCharges ServiceCharges
Subtotal SUM Basis Adjustment Surcharge
TAXOFEIGHTPERCENT FROM Subtotal
Taxes SUM TAXOFEIGHTPERCENT
Total SUM Subtotal Taxes

Table of Contents

Report: Tariff Report

For: FPL_GSD-1_GENERALSERVICEDEMAND

Timestamp: 2024-07-07 15:38:44

General

Parameter
Meter ELECTRICITY:FACILITY
Selected No
Group COMM ELECT
Qualified No
Disqualifier MINDEMAND20KW
Computation automatic
Units kWh


Categories

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
EnergyCharges ($) 314.55 284.08 338.14 351.73 396.41 380.72 409.64 419.87 391.59 391.67 355.11 327.73 4361.24 419.87
DemandCharges ($) 41.12 44.20 49.19 53.63 61.94 65.95 66.67 70.12 64.61 60.90 52.03 51.62 681.97 70.12
ServiceCharges ($) 32.54 32.54 32.54 32.54 32.54 32.54 32.54 32.54 32.54 32.54 32.54 32.54 390.48 32.54
Basis ($) 388.21 360.82 419.87 437.90 490.89 479.20 508.86 522.52 488.74 485.11 439.67 411.89 5433.69 522.52
Adjustment ($) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Surcharge ($) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Subtotal ($) 388.21 360.82 419.87 437.90 490.89 479.20 508.86 522.52 488.74 485.11 439.67 411.89 5433.69 522.52
Taxes ($) 31.06 28.87 33.59 35.03 39.27 38.34 40.71 41.80 39.10 38.81 35.17 32.95 434.70 41.80
Total ($) 419.27 389.69 453.46 472.93 530.16 517.54 549.57 564.32 527.84 523.92 474.85 444.84 5868.39 564.32


Charges

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max Category
NON-FUELENERGYCHARGE ($) 77.93 70.38 83.77 87.14 98.21 94.32 101.49 104.02 97.01 97.03 87.97 81.19 1080.45 104.02 EnergyCharges
FUELENERGYCHARGE ($) 228.09 206.00 245.19 255.05 287.45 276.07 297.05 304.46 283.95 284.01 257.50 237.65 3162.49 304.46 EnergyCharges
CONSERVATIONENERGYCHARGE ($) 7.39 6.68 7.95 8.27 9.32 8.95 9.63 9.87 9.21 9.21 8.35 7.70 102.52 9.87 EnergyCharges
ENVIRONMENTALENERGYCHARGE ($) 1.14 1.03 1.22 1.27 1.43 1.38 1.48 1.52 1.42 1.42 1.28 1.19 15.77 1.52 EnergyCharges
TAXOFEIGHTPERCENT ($) 31.06 28.87 33.59 35.03 39.27 38.34 40.71 41.80 39.10 38.81 35.17 32.95 434.70 41.80 Taxes
ANNUALDEMANDBASECHARGE ($) 28.71 30.86 34.35 37.45 43.25 46.05 46.56 48.96 45.12 42.53 36.33 36.05 476.23 48.96 DemandCharges
ANNUALDEMANDCAPACITYCHARGE ($) 12.40 13.33 14.84 16.18 18.69 19.89 20.11 21.15 19.49 18.37 15.70 15.57 205.74 21.15 DemandCharges


Corresponding Sources for Charges

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
Subtotal 388.21 360.82 419.87 437.90 490.89 479.20 508.86 522.52 488.74 485.11 439.67 411.89 5433.69 522.52
TotalEnergy 5688.15 5137.15 6114.58 6360.41 7168.36 6884.56 7407.68 7592.54 7081.16 7082.61 6421.45 5926.40 78865.05 7592.54
TotalDemand 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43


Ratchets

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max


Qualifies

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
MAXDEMAND500KW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
MINDEMAND20KW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Native Variables

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
TotalEnergy 5688.15 5137.15 6114.58 6360.41 7168.36 6884.56 7407.68 7592.54 7081.16 7082.61 6421.45 5926.40 78865.05 7592.54
TotalDemand 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43
PeakEnergy 5688.15 5137.15 6114.58 6360.41 7168.36 6884.56 7407.68 7592.54 7081.16 7082.61 6421.45 5926.40 78865.05 7592.54
PeakDemand 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43
ShoulderEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ShoulderDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
OffPeakEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
OffPeakDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MidPeakEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MidPeakDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakExceedsOffPeak 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43
OffPeakExceedsPeak 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakExceedsMidPeak 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43
MidPeakExceedsPeak 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakExceedsShoulder 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43
ShoulderExceedsPeak 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsWinter 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
IsNotWinter 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsSpring 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsNotSpring 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
IsSummer 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsNotSummer 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
IsAutumn 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsNotAutumn 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
PeakAndShoulderEnergy 5688.15 5137.15 6114.58 6360.41 7168.36 6884.56 7407.68 7592.54 7081.16 7082.61 6421.45 5926.40 78865.05 7592.54
PeakAndShoulderDemand 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43
PeakAndMidPeakEnergy 5688.15 5137.15 6114.58 6360.41 7168.36 6884.56 7407.68 7592.54 7081.16 7082.61 6421.45 5926.40 78865.05 7592.54
PeakAndMidPeakDemand 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43
ShoulderAndOffPeakEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ShoulderAndOffPeakDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakAndOffPeakEnergy 5688.15 5137.15 6114.58 6360.41 7168.36 6884.56 7407.68 7592.54 7081.16 7082.61 6421.45 5926.40 78865.05 7592.54
PeakAndOffPeakDemand 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43
RealTimePriceCosts 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AboveCustomerBaseCosts 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BelowCustomerBaseCosts 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AboveCustomerBaseEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BelowCustomerBaseEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Other Variables

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
NotIncluded 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Computation - Automatic

MAXDEMAND500KW FROM TotalDemand
MINDEMAND20KW FROM TotalDemand
NON-FUELENERGYCHARGE FROM TotalEnergy
FUELENERGYCHARGE FROM TotalEnergy
CONSERVATIONENERGYCHARGE FROM TotalEnergy
ENVIRONMENTALENERGYCHARGE FROM TotalEnergy
ANNUALDEMANDBASECHARGE FROM TotalDemand
ANNUALDEMANDCAPACITYCHARGE FROM TotalDemand
EnergyCharges SUM NON-FUELENERGYCHARGE FUELENERGYCHARGE CONSERVATIONENERGYCHARGE ENVIRONMENTALENERGYCHARGE
DemandCharges SUM ANNUALDEMANDBASECHARGE ANNUALDEMANDCAPACITYCHARGE
Basis SUM EnergyCharges DemandCharges ServiceCharges
Subtotal SUM Basis Adjustment Surcharge
TAXOFEIGHTPERCENT FROM Subtotal
Taxes SUM TAXOFEIGHTPERCENT
Total SUM Subtotal Taxes

Table of Contents

Report: Tariff Report

For: FPL_GS-1_NONDEMAND

Timestamp: 2024-07-07 15:38:44

General

Parameter
Meter ELECTRICITY:FACILITY
Selected Yes
Group COMM ELECT
Qualified Yes
Disqualifier n/a
Computation automatic
Units kWh


Categories

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
EnergyCharges ($) 531.84 480.32 571.71 594.70 670.24 643.71 692.62 709.90 662.09 662.22 600.41 554.12 7373.88 709.90
DemandCharges ($) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ServiceCharges ($) 8.37 8.37 8.37 8.37 8.37 8.37 8.37 8.37 8.37 8.37 8.37 8.37 100.44 8.37
Basis ($) 540.21 488.69 580.08 603.07 678.61 652.08 700.99 718.27 670.46 670.59 608.78 562.49 7474.32 718.27
Adjustment ($) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Surcharge ($) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Subtotal ($) 540.21 488.69 580.08 603.07 678.61 652.08 700.99 718.27 670.46 670.59 608.78 562.49 7474.32 718.27
Taxes ($) 43.22 39.10 46.41 48.25 54.29 52.17 56.08 57.46 53.64 53.65 48.70 45.00 597.95 57.46
Total ($) 583.43 527.79 626.49 651.31 732.90 704.24 757.07 775.73 724.10 724.24 657.48 607.49 8072.27 775.73


Charges

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max Category
NON-FUELENERGYCHARGE ($) 219.56 198.29 236.02 245.51 276.70 265.74 285.94 293.07 273.33 273.39 247.87 228.76 3044.19 293.07 EnergyCharges
FUELENERGYCHARGE ($) 232.65 210.11 250.09 260.14 293.19 281.58 302.97 310.53 289.62 289.68 262.64 242.39 3225.58 310.53 EnergyCharges
CONSERVATION ($) 7.96 7.19 8.56 8.90 10.04 9.64 10.37 10.63 9.91 9.92 8.99 8.30 110.41 10.63 EnergyCharges
CAPACITY ($) 35.84 32.36 38.52 40.07 45.16 43.37 46.67 47.83 44.61 44.62 40.46 37.34 496.85 47.83 EnergyCharges
TAXOFEIGHTPERCENT ($) 43.22 39.10 46.41 48.25 54.29 52.17 56.08 57.46 53.64 53.65 48.70 45.00 597.95 57.46 Taxes


Corresponding Sources for Charges

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
Subtotal 540.21 488.69 580.08 603.07 678.61 652.08 700.99 718.27 670.46 670.59 608.78 562.49 7474.32 718.27
TotalEnergy 5688.15 5137.15 6114.58 6360.41 7168.36 6884.56 7407.68 7592.54 7081.16 7082.61 6421.45 5926.40 78865.05 7592.54


Ratchets

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max


Qualifies

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
MAXDEMAND20KW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00


Native Variables

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
TotalEnergy 5688.15 5137.15 6114.58 6360.41 7168.36 6884.56 7407.68 7592.54 7081.16 7082.61 6421.45 5926.40 78865.05 7592.54
TotalDemand 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43
PeakEnergy 5688.15 5137.15 6114.58 6360.41 7168.36 6884.56 7407.68 7592.54 7081.16 7082.61 6421.45 5926.40 78865.05 7592.54
PeakDemand 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43
ShoulderEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ShoulderDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
OffPeakEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
OffPeakDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MidPeakEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MidPeakDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakExceedsOffPeak 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43
OffPeakExceedsPeak 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakExceedsMidPeak 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43
MidPeakExceedsPeak 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakExceedsShoulder 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43
ShoulderExceedsPeak 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsWinter 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
IsNotWinter 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsSpring 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsNotSpring 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
IsSummer 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsNotSummer 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
IsAutumn 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsNotAutumn 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
PeakAndShoulderEnergy 5688.15 5137.15 6114.58 6360.41 7168.36 6884.56 7407.68 7592.54 7081.16 7082.61 6421.45 5926.40 78865.05 7592.54
PeakAndShoulderDemand 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43
PeakAndMidPeakEnergy 5688.15 5137.15 6114.58 6360.41 7168.36 6884.56 7407.68 7592.54 7081.16 7082.61 6421.45 5926.40 78865.05 7592.54
PeakAndMidPeakDemand 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43
ShoulderAndOffPeakEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ShoulderAndOffPeakDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakAndOffPeakEnergy 5688.15 5137.15 6114.58 6360.41 7168.36 6884.56 7407.68 7592.54 7081.16 7082.61 6421.45 5926.40 78865.05 7592.54
PeakAndOffPeakDemand 14.94 15.31 15.91 16.45 17.44 17.93 18.01 18.43 17.77 17.32 16.25 16.20 201.97 18.43
RealTimePriceCosts 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AboveCustomerBaseCosts 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BelowCustomerBaseCosts 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AboveCustomerBaseEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BelowCustomerBaseEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Other Variables

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
NotIncluded 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Computation - Automatic

MAXDEMAND20KW FROM TotalDemand
NON-FUELENERGYCHARGE FROM TotalEnergy
FUELENERGYCHARGE FROM TotalEnergy
CONSERVATION FROM TotalEnergy
CAPACITY FROM TotalEnergy TotalEnergy
EnergyCharges SUM NON-FUELENERGYCHARGE FUELENERGYCHARGE CONSERVATION CAPACITY CAPACITY
Basis SUM EnergyCharges DemandCharges ServiceCharges
Subtotal SUM Basis Adjustment Surcharge
TAXOFEIGHTPERCENT FROM Subtotal
Taxes SUM TAXOFEIGHTPERCENT
Total SUM Subtotal Taxes

Table of Contents

Report: Tariff Report

For: FL_EIAMONTHLYRATEGAS

Timestamp: 2024-07-07 15:38:44

General

Parameter
Meter GAS:FACILITY
Selected Yes
Group COMM GAS
Qualified Yes
Disqualifier n/a
Computation automatic
Units MCF


Categories

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
EnergyCharges ($) 9.70 8.74 9.65 9.02 9.37 9.30 9.76 9.35 9.17 9.34 8.41 9.25 111.06 9.76
DemandCharges ($) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ServiceCharges ($) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Basis ($) 9.70 8.74 9.65 9.02 9.37 9.30 9.76 9.35 9.17 9.34 8.41 9.25 111.06 9.76
Adjustment ($) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Surcharge ($) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Subtotal ($) 9.70 8.74 9.65 9.02 9.37 9.30 9.76 9.35 9.17 9.34 8.41 9.25 111.06 9.76
Taxes ($) 0.7761 0.6992 0.7717 0.7213 0.7499 0.7440 0.7809 0.7482 0.7337 0.7472 0.6726 0.7404 8.89 0.78
Total ($) 10.48 9.44 10.42 9.74 10.12 10.04 10.54 10.10 9.91 10.09 9.08 9.99 119.95 10.54


Charges

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max Category
MONTHLYRATEGASCHARGE ($) 9.70 8.74 9.65 9.02 9.37 9.30 9.76 9.35 9.17 9.34 8.41 9.25 111.06 9.76 EnergyCharges
TAXOFEIGHTPERCENT ($) 0.7761 0.6992 0.7717 0.7213 0.7499 0.7440 0.7809 0.7482 0.7337 0.7472 0.6726 0.7404 8.89 0.78 Taxes


Corresponding Sources for Charges

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
Subtotal 9.70 8.74 9.65 9.02 9.37 9.30 9.76 9.35 9.17 9.34 8.41 9.25 111.06 9.76
TotalEnergy 0.8693 0.7742 0.8559 0.8079 0.8281 0.7997 0.8286 0.8269 0.8088 0.8399 0.8116 0.8617 9.91 0.87


Ratchets

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max


Qualifies

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max


Native Variables

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
TotalEnergy 0.8693 0.7742 0.8559 0.8079 0.8281 0.7997 0.8286 0.8269 0.8088 0.8399 0.8116 0.8617 9.91 0.87
TotalDemand 0.0100 0.0065 0.0077 0.0039 0.0034 0.0034 0.0035 0.0034 0.0035 0.0034 0.0068 0.0076 0.06 0.01
PeakEnergy 0.8693 0.7742 0.8559 0.8079 0.8281 0.7997 0.8286 0.8269 0.8088 0.8399 0.8116 0.8617 9.91 0.87
PeakDemand 0.0100 0.0065 0.0077 0.0039 0.0034 0.0034 0.0035 0.0034 0.0035 0.0034 0.0068 0.0076 0.06 0.01
ShoulderEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ShoulderDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
OffPeakEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
OffPeakDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MidPeakEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MidPeakDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakExceedsOffPeak 0.0100 0.0065 0.0077 0.0039 0.0034 0.0034 0.0035 0.0034 0.0035 0.0034 0.0068 0.0076 0.06 0.01
OffPeakExceedsPeak 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakExceedsMidPeak 0.0100 0.0065 0.0077 0.0039 0.0034 0.0034 0.0035 0.0034 0.0035 0.0034 0.0068 0.0076 0.06 0.01
MidPeakExceedsPeak 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakExceedsShoulder 0.0100 0.0065 0.0077 0.0039 0.0034 0.0034 0.0035 0.0034 0.0035 0.0034 0.0068 0.0076 0.06 0.01
ShoulderExceedsPeak 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsWinter 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
IsNotWinter 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsSpring 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsNotSpring 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
IsSummer 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsNotSummer 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
IsAutumn 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
IsNotAutumn 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 12.00 1.00
PeakAndShoulderEnergy 0.8693 0.7742 0.8559 0.8079 0.8281 0.7997 0.8286 0.8269 0.8088 0.8399 0.8116 0.8617 9.91 0.87
PeakAndShoulderDemand 0.0100 0.0065 0.0077 0.0039 0.0034 0.0034 0.0035 0.0034 0.0035 0.0034 0.0068 0.0076 0.06 0.01
PeakAndMidPeakEnergy 0.8693 0.7742 0.8559 0.8079 0.8281 0.7997 0.8286 0.8269 0.8088 0.8399 0.8116 0.8617 9.91 0.87
PeakAndMidPeakDemand 0.0100 0.0065 0.0077 0.0039 0.0034 0.0034 0.0035 0.0034 0.0035 0.0034 0.0068 0.0076 0.06 0.01
ShoulderAndOffPeakEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ShoulderAndOffPeakDemand 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PeakAndOffPeakEnergy 0.8693 0.7742 0.8559 0.8079 0.8281 0.7997 0.8286 0.8269 0.8088 0.8399 0.8116 0.8617 9.91 0.87
PeakAndOffPeakDemand 0.0100 0.0065 0.0077 0.0039 0.0034 0.0034 0.0035 0.0034 0.0035 0.0034 0.0068 0.0076 0.06 0.01
RealTimePriceCosts 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AboveCustomerBaseCosts 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BelowCustomerBaseCosts 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AboveCustomerBaseEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BelowCustomerBaseEnergy 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Other Variables

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Sum Max
NotIncluded 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FL_MONTHLYGASRATES 11.16 11.29 11.27 11.16 11.32 11.63 11.78 11.31 11.34 11.12 10.36 10.74 134.48 11.78


Computation - Automatic

MONTHLYRATEGASCHARGE FROM TotalEnergy FL_MONTHLYGASRATES
EnergyCharges SUM MONTHLYRATEGASCHARGE
Basis SUM EnergyCharges DemandCharges ServiceCharges
Subtotal SUM Basis Adjustment Surcharge
TAXOFEIGHTPERCENT FROM Subtotal
Taxes SUM TAXOFEIGHTPERCENT
Total SUM Subtotal Taxes